Facility Data Loaded: Holiday Inn Petersburg Virginia.txt
Copy and paste this data into an email, spreadsheet, or document for your records.
0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | |||||
Room Panel Num |
Room Name | Room Length (ft-in) |
Room Width (ft-in) |
Room Height (ft-in) |
Vent Length (in) |
Vent Width or Diameter (in) |
Vent Air ft/min (ventA + ventB + ventC + ventD*2 + ventE*4...) |
Room sq-ft |
Room cu-ft |
Vent CFM cuft/min |
Vent CFH cuft/hr |
Num of Vents |
Control Zone # |
Vents Clear yes no |
System ON yes no fail |
eACH UV-C |
eACH Far UV |
ACH Other wACH eACH |
ACH Total |
|
1. | Low fan | 24 | 12 | 8 | 4 | 30 | 643 | 288 | 2304 | 535.8 | 32148 | 1 | A | Yes | Yes | 13.9 | ||||
2. | High fan | 24 | 12 | 8 | 4 | 30 | 712 | 288 | 2304 | 593.3 | 35598 | 1 | A | Yes | Yes | 15.4 | ||||
3. | Hall | 180 | 6 | 8 | 4 | 30 | 712*2 | 1080 | 8640 | 1186.6 | 71196 | 2 | B&C | No | Yes | 8.2 | ||||
Total Space Aggregate | 1656 | 13248 | 2315.7 | 138942 | 4 | |||||||||||||||
Max | - | - | - | - | - | - | - | - | ||||||||||||
includes 0 Min | - | - | - | - | - | - | - | - | ||||||||||||
excludes 0 Lowest | - | - | - | - | - | - | - | - | ||||||||||||
Average ACH affected by room sizes | - | - | - | - | - | - | - | - | ||||||||||||
Facility Panel R |
Multiple Vents Analysis | na | na | na | 0 | 0 | 2315.7 | 138942 | 4 |
ACH Report end
Does not include facilities with Caution Status because there is no ACH data
Low |
Low |
|||||||||||||||||
with ACH Levels |
most risk | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15+ | least risk |
3 | 1 | 1 | 1 | |||||||||||||||
100% | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 33.3 | 0 | 0 | 0 | 0 | 33.3 | 0 | 33.3 | ||
3 | 1 | 1 | 1 | |||||||||||||||
100% | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 33.3 | 0 | 0 | 0 | 0 | 33.3 | 0 | 33.3 | ||
Facility Name and Location: Holiday Inn Petersburg Virginia
Comments: 12 ft x 4 ft ceiling panels 5 panels + 1 panel for entry 24 ft. New GE in room unit ventilators replaced standalone room hvac units. Building modified for in room units. Room hvac unit vents still visible and thermostats still on walls. Ceiling vents sealed. Hall 90 2 ft tiles x 3 2 ft tiles 180 x 6 ft 2 GE unit ventilators in hall. Unit ventilators in hall are not appropriate because the hall is too long. There is huge dead air spot in center of hall. Unit ventilators effective for approximately 20 feet.
Benefit Report end