Facility Data Loaded: MCO Orlando International Airport.txt
Copy and paste this data into an email, spreadsheet, or document for your records.
0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | |||||
Room Panel Num |
Room Name | Room Length (ft-in) |
Room Width (ft-in) |
Room Height (ft-in) |
Vent Length (in) |
Vent Width or Diameter (in) |
Vent Air ft/min (ventA + ventB + ventC + ventD*2 + ventE*4...) |
Room sq-ft |
Room cu-ft |
Vent CFM cuft/min |
Vent CFH cuft/hr |
Num of Vents |
Control Zone # |
Vents Clear yes no |
System ON yes no fail |
eACH UV-C |
eACH Far UV |
ACH Other wACH eACH |
ACH Total |
|
1. | Seating Area | na cuft | na cuft | na cuft | na | na | na | na cuft | 7000000 | cfm | 0 | 1 | zone | 4.7 | 4.7 | |||||
Total Space Aggregate | 0 | 7000000 | 0 | 0 | 1 | |||||||||||||||
Max | - | - | - | - | - | - | - | - | ||||||||||||
includes 0 Min | - | - | - | - | - | - | - | - | ||||||||||||
excludes 0 Lowest | - | - | - | - | - | - | - | - | ||||||||||||
Average ACH affected by room sizes | - | - | - | - | - | - | - | - | ||||||||||||
Facility Panel R |
Multiple Vents Analysis | bld l | bld w | bld h | na | na | na | 0 | 0 | 0 | 0 | 1 |
ACH Report end
Does not include facilities with Caution Status because there is no ACH data
Low |
Low |
|||||||||||||||||
with ACH Levels |
most risk | 0 | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15+ | least risk |
1 | 1 | |||||||||||||||||
100% | 100 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | ||
1 | 1 | |||||||||||||||||
100% | 0 | 0 | 0 | 0 | 100 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 | ||
Facility Name and Location: MCO Orlando International Airport
Comments: 374 air handling units (AHUs) and 287 fan coil units (FCUs) supply conditioned air, AHUs push nearly 11 million cubic feet of air each minute, There are over 12,000 filters in the AHUs, 28 chilled water units provide cooling throughout the airport, With a total capacity of over 21,000 tonnes, our chillers are equivalent to 5,250 homes. Both staff and machines monitor air quality through all facilities and maintain optimal climate control. The system helps maintain the comfort level of the passengers and helps keep the air cleaner, said Assistant Director of Maintenance for the Greater Orlando Aviation Authority. The UV lights help sterilise the air that sits on the cool water coils and the filtration system will certainly keep most of the particulates down. https://www.internationalairportreview.com/news/122361/air-quality-orlando-airport-covid19
With more than seven million square feet under roof: https://www.orlandoairports.net/press/2020/07/31/managing-air-quality-is-a-top-priority-at-orlando-international-airport.
Assuming average ceiling height is 20 feet. 4.7 ACH = ((11000000*60)/(7000000*20)
From 2017, MERV-8+ filters. Outside air Section 4 through 7 of ASHRAE Standard 62.1-2010. https://orlandoairports.net/site/uploads/STC-Passenger-Lounge-RFP-Volume-C-MCO-Tenant-Design-Criteria-Volume-3-Design-Criteria.pdf. http://arco-hvac.ir/wp-content/uploads/2016/04/ASHRAE-62_1-2010.pdf