Clean Air Building Certificate

Space Type: BOS-School
Establishment Name: Eliot John K 1 Commercial St
Address: address
City: Boston
State / Province: MA
Country: USA
Date: 03/21/2021
Data Source: School District
Performed by: External Company
Company Name Address Contact: Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
Requirement Source: Boston School 3 ACH guideline

Technology: Central HVAC
Min ACH: 2.7 Max ACH: 4.9 Avg ACH: 3.4 eACH: 0
Filter MERV: ---
Percent Outside Air: 100
ON and Ventilates Entire Indoor Area: Yes
Vent Clearance min 6 ft: Yes
No of Rooms: 6 sqft: 1134 cuft: 11340 No of Buildings: 1

Comments: Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 202. Diffuser air volume (cfm) 345. % Outside air 100. Calculated air volume (cfm) outside 345. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 345. ACH outside 4.9. ACH total 4.9. ACH Copy paste check (uses total or outside) 4.9.

Room 206. Diffuser air volume (cfm) 264. % Outside air 100. Calculated air volume (cfm) outside 264. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 264. ACH outside 2.9. ACH total 2.9. ACH Copy paste check (uses total or outside) 2.9.

Room 316. Diffuser air volume (cfm) 252. % Outside air 100. Calculated air volume (cfm) outside 252. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 252. ACH outside 3.2. ACH total 3.2. ACH Copy paste check (uses total or outside) 3.2.

Room 403. Diffuser air volume (cfm) 296. % Outside air 100. Calculated air volume (cfm) outside 296. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 296. ACH outside 3.8. ACH total 3.8. ACH Copy paste check (uses total or outside) 3.8.

Room 408. Diffuser air volume (cfm) 263. % Outside air 100. Calculated air volume (cfm) outside 263. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 263. ACH outside 2.7. ACH total 2.7. ACH Copy paste check (uses total or outside) 2.7.

Room 102. Diffuser air volume (cfm) 225. % Outside air 100. Calculated air volume (cfm) outside 225. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 225. ACH outside 1.2. ACH total 1.2. ACH Copy paste check (uses total or outside) 1.2.

In the wake of the COVID-19 disaster many are calling for a paradigm shift in how citizens and government officials think about the quality of the air we breathe indoors. This Clean Air Certificate lets you know that those who operate this building are thinking about the air that we breathe in this building. They have disclosed the ventilation performance of this building so that we all become educated and we never have another indoor infection disaster again.

Serial Number: CAB-1633-05152025
Not valid without serial number.