Clean Air Building Certificate Space Type: BOS-School
Establishment Name: Muniz Margarite Academy
Address: address
City: Boston
State / Province: MA
Country: USA
Date: 03/21/2021
Data Source: School District
Performed by: External Company
Company Name Address Contact: Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
Requirement Source: Boston School 3 ACH guideline
Technology: Central HVAC
Min ACH: 1.8 Max ACH: 9.9 Avg ACH: 4.1 eACH: 0 Filter MERV: 13
Percent Outside Air: 100
ON and Ventilates Entire Indoor Area: Yes
Vent Clearance min 6 ft: Yes
No of Rooms: 6 sqft: 579.6 cuft: 5796 No of Buildings: 1
Comments: Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.
Room 105. Diffuser air volume (cfm) 890. % Outside air 100. Calculated air volume (cfm) outside 890. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 890. ACH outside 9.9. ACH total 9.9. Room 108. Diffuser air volume (cfm) 394. % Outside air 100. Calculated air volume (cfm) outside 394. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 394. ACH outside 2.1. ACH total 2.1. Room 306. Diffuser air volume (cfm) 290. % Outside air 100. Calculated air volume (cfm) outside 290. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 290. ACH outside 3.9. ACH total 3.9. Room 308. Diffuser air volume (cfm) 300. % Outside air 100. Calculated air volume (cfm) outside 300. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 300. ACH outside 3.6. ACH total 3.6. Room 315. Diffuser air volume (cfm) 250. % Outside air 100. Calculated air volume (cfm) outside 250. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 250. ACH outside 1.8. ACH total 1.8. Room 108. Diffuser air volume (cfm) 262. % Outside air 50. Calculated air volume (cfm) outside 131. Calculated air volume (cfm) return 131. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 242. ACH outside 1.4. ACH merv filter return air 1.15. ACH total 2.55.
In the wake of the COVID-19 disaster many are calling for a paradigm shift in how citizens and government officials think about the quality of the air we breathe indoors.
This Clean Air Certificate lets you know that those who operate this building are thinking about the air that we breathe in this building.
They have disclosed the ventilation performance of this building so that we all become educated and we never have another indoor infection disaster again.
|