Clean Air Building Certificate Space Type: BOS-School
Establishment Name: Murphy Richard J K 8
Address: address
City: Boston
State / Province: MA
Country: USA
Date: 03/21/2021
Data Source: School District
Performed by: External Company
Company Name Address Contact: Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
Requirement Source: Boston School 3 ACH guideline
Technology: Central HVAC
Min ACH: 2.55 Max ACH: 3.48 Avg ACH: 2.9 eACH: 0 Filter MERV: 13
Percent Outside Air: 50
ON and Ventilates Entire Indoor Area: Yes
Vent Clearance min 6 ft: Yes
No of Rooms: 3 sqft: 705.6 cuft: 7056 No of Buildings: 1
Comments: Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.
Room 116. Diffuser air volume (cfm) 533. % Outside air 50. Calculated air volume (cfm) outside 266.5. Calculated air volume (cfm) return 266.5. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 493. ACH outside 1.6. ACH merv filter return air 1.32. ACH total 2.92. Room 216. Diffuser air volume (cfm) 377. % Outside air 50. Calculated air volume (cfm) outside 188.5. Calculated air volume (cfm) return 188.5. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 349. ACH outside 1.9. ACH merv filter return air 1.58. ACH total 3.48. Room 3-B27. Diffuser air volume (cfm) 200. % Outside air 50. Calculated air volume (cfm) outside 100. Calculated air volume (cfm) return 100. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 185. ACH outside 0.9. ACH merv filter return air 0.7. ACH total 1.6.