Clean Air Building Certificate Space Type: BOS-School
Establishment Name: Haley Dennis Pilot School K 8
Address: address
City: Boston
State / Province: MA
Country: USA
Date: 03/21/2021
Data Source: School District
Performed by: External Company
Company Name Address Contact: Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
Requirement Source: Boston School 3 ACH guideline
Technology: Natural Ventilation Windows and Limited HVAC
Min ACH: 0.9 Max ACH: 6.4 Avg ACH: 3.1 eACH: 0 Filter MERV: ---
Percent Outside Air: 69.7
ON and Ventilates Entire Indoor Area: Yes
Vent Clearance min 6 ft: Yes
No of Rooms: 4 sqft: 800.4 cuft: 8004 No of Buildings: 1
Comments: Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.
Room 129. Diffuser air volume (cfm) 536. % Outside air 70. Calculated air volume (cfm) outside 375. Calculated air volume (cfm) return 161. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 512. ACH outside 2.9. ACH merv filter return air 1.2. ACH total 3.9. ACH Copy paste check (uses total or outside) 3.3. Room 130. Diffuser air volume (cfm) 311. % Outside air 70. Calculated air volume (cfm) outside 218. Calculated air volume (cfm) return 93. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 297. ACH outside 1.0. ACH merv filter return air 0.4. ACH total 1.3. ACH Copy paste check (uses total or outside) 1.4. Room 158. Diffuser air volume (cfm) 625. % Outside air 70. Calculated air volume (cfm) outside 437. Calculated air volume (cfm) return 187. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 596. ACH outside 4.7. ACH merv filter return air 2.0. ACH total 6.4. ACH Copy paste check (uses total or outside) 6.4. Room 101. Diffuser air volume (cfm) 247. % Outside air 100. Calculated air volume (cfm) outside 247. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 247. ACH outside 1.9. ACH merv filter return air 0.0. ACH total 1.9. ACH Copy paste check (uses total or outside) 1.9.
In the wake of the COVID-19 disaster many are calling for a paradigm shift in how citizens and government officials think about the quality of the air we breathe indoors.
This Clean Air Certificate lets you know that those who operate this building are thinking about the air that we breathe in this building.
They have disclosed the ventilation performance of this building so that we all become educated and we never have another indoor infection disaster again.
|