Clean Air Building Certificate

Space Type: BOS-School
Establishment Name: Bradley Manassah E Elem
Address: address
City: Boston
State / Province: MA
Country: USA
Date: 03/21/2021
Data Source: School District
Performed by: External Company
Company Name Address Contact: Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
Requirement Source: Boston School 3 ACH guideline

Technology: Natural Ventilation Windows and Limited Univent HVAC
Min ACH: 2.2 Max ACH: 4 Avg ACH: 2.9 eACH: 0
Filter MERV:
Percent Outside Air: 66.1
ON and Ventilates Entire Indoor Area: Yes
Vent Clearance min 6 ft: Yes
No of Rooms: 6 sqft: 926.9 cuft: 9269 No of Buildings: 1

Comments: Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 206. % Outside air 68. Calculated air volume (cfm) outside 390. Calculated air volume (cfm) return 180. Combined air volume (cfm) 570. ACH outside 2.7. ACH merv filter return air 1.3. ACH total 4.0. ACH Copy paste check (uses total or outside) 2.7.

Room 212. % Outside air 54. Calculated air volume (cfm) outside 227. Calculated air volume (cfm) return 193. Combined air volume (cfm) 420. ACH outside 2.0. ACH merv filter return air 1.7. ACH total 3.7. ACH Copy paste check (uses total or outside) 2.

Room 103. % Outside air 79. Calculated air volume (cfm) outside 325. Calculated air volume (cfm) return 85. Combined air volume (cfm) 410. ACH outside 2.2. ACH merv filter return air 0.6. ACH total 2.7. ACH Copy paste check (uses total or outside) 2.2.

Room 101. % Outside air 68. Calculated air volume (cfm) outside 282. Calculated air volume (cfm) return 133. Combined air volume (cfm) 415. ACH outside 1.9. ACH merv filter return air 0.9. ACH total 2.8. ACH Copy paste check (uses total or outside) 1.9.

Room 105. % Outside air 73. Calculated air volume (cfm) outside 235. Calculated air volume (cfm) return 85. Combined air volume (cfm) 320. ACH outside 1.6. ACH merv filter return air 0.6. ACH total 2.2. ACH Copy paste check (uses total or outside) 1.5.

Room 221. % Outside air 10. Calculated air volume (cfm) outside 80. Calculated air volume (cfm) return 650. Combined air volume (cfm) 730. ACH outside 0.5. ACH merv filter return air 4.2. ACH total 4.7. ACH Copy paste check (uses total or outside) 0.5.

In the wake of the COVID-19 disaster many are calling for a paradigm shift in how citizens and government officials think about the quality of the air we breathe indoors. This Clean Air Certificate lets you know that those who operate this building are thinking about the air that we breathe in this building. They have disclosed the ventilation performance of this building so that we all become educated and we never have another indoor infection disaster again.

Serial Number: CAB-1691-05162025
Not valid without serial number.