Clean Air Building Certificate

Space Type: BOS-School
Establishment Name: Kennedy John F Elem
Address: address
City: Boston
State / Province: MA
Country: USA
Date: 03/21/2021
Data Source: School District
Performed by: External Company
Company Name Address Contact: Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
Requirement Source: Boston School 3 ACH guideline

Technology: Natural Ventilation Windows and Limited Univent HVAC
Min ACH: 2.9 Max ACH: 4.7 Avg ACH: 4 eACH: 0
Filter MERV:
Percent Outside Air: 12.5
ON and Ventilates Entire Indoor Area: Yes
Vent Clearance min 6 ft: Yes
No of Rooms: 6 sqft: 1014 cuft: 10140 No of Buildings: 1

Comments: Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 104. % Outside air 24. Calculated air volume (cfm) outside 126. Calculated air volume (cfm) return 394. Combined air volume (cfm) 520. ACH outside 1.0. ACH merv filter return air 3.3. ACH total 4.3. ACH Copy paste check (uses total or outside) 1.

Room 107. % Outside air 13. Calculated air volume (cfm) outside 68. Calculated air volume (cfm) return 465. Combined air volume (cfm) 533. ACH outside 0.6. ACH merv filter return air 3.8. ACH total 4.4. ACH Copy paste check (uses total or outside) 0.6.

Room 208. % Outside air 2. Calculated air volume (cfm) outside 13. Calculated air volume (cfm) return 522. Combined air volume (cfm) 535. ACH outside 0.1. ACH merv filter return air 4.3. ACH total 4.4. ACH Copy paste check (uses total or outside) 0.1.

Room 205. % Outside air 29. Calculated air volume (cfm) outside 101. Calculated air volume (cfm) return 252. Combined air volume (cfm) 353. ACH outside 0.8. ACH merv filter return air 2.1. ACH total 2.9. ACH Copy paste check (uses total or outside) 0.8.

Room 201. % Outside air 9. Calculated air volume (cfm) outside 46. Calculated air volume (cfm) return 445. Combined air volume (cfm) 491. ACH outside 0.4. ACH merv filter return air 4.2. ACH total 4.7. ACH Copy paste check (uses total or outside) 0.4.

Room 105. % Outside air 55. Calculated air volume (cfm) outside 308. Calculated air volume (cfm) return 249. Combined air volume (cfm) 557. ACH outside 1.8. ACH merv filter return air 1.5. ACH total 3.3. ACH Copy paste check (uses total or outside) 1.8.

In the wake of the COVID-19 disaster many are calling for a paradigm shift in how citizens and government officials think about the quality of the air we breathe indoors. This Clean Air Certificate lets you know that those who operate this building are thinking about the air that we breathe in this building. They have disclosed the ventilation performance of this building so that we all become educated and we never have another indoor infection disaster again.

Serial Number: CAB-1703-05162025
Not valid without serial number.