0. Space TypeBOS-School
1. Establishment NameBoston Arts Academy
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyCentral HVAC
12. Min ACH1.7
13. Max ACH10.2
14. Avg ACH4.7
15. eACH0
16. Filter MERV85
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft691.2
22. cuft6912
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room A006. Diffuser air volume (cfm) 1115. % Outside air 100. Calculated air volume (cfm) outside 1115. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 1115. ACH outside 7.6. ACH total 7.6. ACH Copy paste check (uses total or outside) 7.6.

Room A101. Diffuser air volume (cfm) 303. % Outside air 100. Calculated air volume (cfm) outside 303. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 303. ACH outside 2.1. ACH total 2.1. ACH Copy paste check (uses total or outside) 2.1.

Room A102. Diffuser air volume (cfm) 280. % Outside air 100. Calculated air volume (cfm) outside 280. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 280. ACH outside 1.7. ACH total 1.7. ACH Copy paste check (uses total or outside) 1.7.

Room A205. Diffuser air volume (cfm) 455. % Outside air 100. Calculated air volume (cfm) outside 455. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 455. ACH outside 3.2. ACH total 3.2. ACH Copy paste check (uses total or outside) 3.2.

Room A220. Diffuser air volume (cfm) 570. % Outside air 100. Calculated air volume (cfm) outside 570. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 570. ACH outside 3.6. ACH total 3.6. ACH Copy paste check (uses total or outside) 3.6.

Room 12. Diffuser air volume (cfm) 1670. % Outside air 50. Calculated air volume (cfm) outside 835. Calculated air volume (cfm) return 835. Filter merv rating 85. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 1545. ACH outside 7.2. ACH merv filter return air 6.2. ACH total 13.4. ACH Copy paste check (uses total or outside) 13.4.