About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameCharlestown High School
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyCentral HVAC
12. Min ACH1.8
13. Max ACH4.1
14. Avg ACH2.8
15. eACH0
16. Filter MERV---
17. Percent Outside Air69.8
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1056
22. cuft10560
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 207. Diffuser air volume (cfm) 910. % Outside air 70. Calculated air volume (cfm) outside 637. Calculated air volume (cfm) return 274. Filter merv rating 85. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 870. ACH outside 1.9. ACH merv filter return air 0.7. ACH total 2.6. ACH Copy paste check (uses total or outside) 2.6.

Room 306. Diffuser air volume (cfm) 300. % Outside air 70. Calculated air volume (cfm) outside 210. Calculated air volume (cfm) return 90. Filter merv rating 85. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 287. ACH outside 1.5. ACH merv filter return air 0.55. ACH total 2.05. ACH Copy paste check (uses total or outside) 2.1.

Room 402. Diffuser air volume (cfm) 740. % Outside air 70. Calculated air volume (cfm) outside 518. Calculated air volume (cfm) return 222. Filter merv rating 85. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 707. ACH outside 2.7. ACH merv filter return air 1. ACH total 3.7. ACH Copy paste check (uses total or outside) 3.7.

Room 409. Diffuser air volume (cfm) 500. % Outside air 70. Calculated air volume (cfm) outside 350. Calculated air volume (cfm) return 150. Filter merv rating 85. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 478. ACH outside 1.3. ACH merv filter return air 0.5. ACH total 1.8. ACH Copy paste check (uses total or outside) 1.8.

Room 539. Diffuser air volume (cfm) 680. % Outside air 70. Calculated air volume (cfm) outside 476. Calculated air volume (cfm) return 204. Filter merv rating 85. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 649. ACH outside 1.9. ACH merv filter return air 0.69. ACH total 2.59. ACH Copy paste check (uses total or outside) 2.6.

Room 200. Diffuser air volume (cfm) 185. % Outside air 100. Calculated air volume (cfm) outside 185. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 185. ACH outside 1.1. ACH total 1.1. ACH Copy paste check (uses total or outside) 1.1.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Charlestown High School.txt. Feel free to add Survey data. Charlestown High School

CAB v 0.11 R -1

23:30:28 Start Time
23:30:28 End Time
0 Seconds

5.026003 cab pid: 358609 httpd pid: error pid: