0. Space TypeBOS-School
1. Establishment NameComm Acad of Science Health
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyCentral HVAC
12. Min ACH0.7
13. Max ACH1.3
14. Avg ACH0.9
15. eACH0
16. Filter MERV13
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1113.6
22. cuft11136
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 216. Diffuser air volume (cfm) 140. % Outside air 100. Calculated air volume (cfm) outside 140. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 140. ACH outside 1. ACH total 1. ACH Copy paste check (uses total or outside) 1.

Room 218. Diffuser air volume (cfm) 110. % Outside air 100. Calculated air volume (cfm) outside 110. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 110. ACH outside 0.8. ACH total 0.8. ACH Copy paste check (uses total or outside) 0.8.

Room 318. Diffuser air volume (cfm) 160. % Outside air 100. Calculated air volume (cfm) outside 160. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 160. ACH outside 0.9. ACH total 0.9. ACH Copy paste check (uses total or outside) 0.9.

Room 320. Diffuser air volume (cfm) 115. % Outside air 100. Calculated air volume (cfm) outside 115. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 115. ACH outside 0.7. ACH total 0.7. ACH Copy paste check (uses total or outside) 0.7.

Room 321. Diffuser air volume (cfm) 185. % Outside air 100. Calculated air volume (cfm) outside 185. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 185. ACH outside 1.3. ACH total 1.3. ACH Copy paste check (uses total or outside) 1.3.

Room 103. Diffuser air volume (cfm) 1740. % Outside air 70. Calculated air volume (cfm) outside 1218. Calculated air volume (cfm) return 522. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 1662. ACH outside 6.5. ACH merv filter return air 2.4. ACH total 8.9. ACH Copy paste check (uses total or outside) 8.9.