Building Data Report

0. Space TypeBOS-School
1. Establishment NameCondon James F K 8
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyCentral HVAC
12. Min ACH7.6
13. Max ACH18
14. Avg ACH13.1
15. eACH0
16. Filter MERV--
17. Percent Outside Air69.8
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1344
22. cuft13440
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 105. Diffuser air volume (cfm) 1733. % Outside air 70. Calculated air volume (cfm) outside 1213. Calculated air volume (cfm) return 520. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 1655. ACH outside 8.9. ACH merv filter return air 3.2. ACH total 12.1. ACH Copy paste check (uses total or outside) 12.1.

Room 203. Diffuser air volume (cfm) 2401. % Outside air 70. Calculated air volume (cfm) outside 1682. Calculated air volume (cfm) return 720. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 2294. ACH outside 12. ACH merv filter return air 4.3. ACH total 16.3. ACH Copy paste check (uses total or outside) 16.3.

Room 214. Diffuser air volume (cfm) 1276. % Outside air 70. Calculated air volume (cfm) outside 894. Calculated air volume (cfm) return 382. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 1219. ACH outside 5.6. ACH merv filter return air 2. ACH total 7.6. ACH Copy paste check (uses total or outside) 7.6.

Room 314. Diffuser air volume (cfm) 2587. % Outside air 70. Calculated air volume (cfm) outside 1811. Calculated air volume (cfm) return 776. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 2471. ACH outside 11.7. ACH merv filter return air 4.2. ACH total 15.9. ACH Copy paste check (uses total or outside) 15.9.

Room 316. Diffuser air volume (cfm) 2964. % Outside air 70. Calculated air volume (cfm) outside 2075. Calculated air volume (cfm) return 889. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 2831. ACH outside 13.2. ACH merv filter return air 4.8. ACH total 18. ACH Copy paste check (uses total or outside) 18.

Room 252. Diffuser air volume (cfm) 307. % Outside air 100. Calculated air volume (cfm) outside 307. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 307. ACH outside 1.4. ACH total 1.4. ACH Copy paste check (uses total or outside) 1.4.