About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameEliot John K 1 Commercial St
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyCentral HVAC
12. Min ACH2.7
13. Max ACH4.9
14. Avg ACH3.4
15. eACH0
16. Filter MERV---
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1134
22. cuft11340
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 202. Diffuser air volume (cfm) 345. % Outside air 100. Calculated air volume (cfm) outside 345. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 345. ACH outside 4.9. ACH total 4.9. ACH Copy paste check (uses total or outside) 4.9.

Room 206. Diffuser air volume (cfm) 264. % Outside air 100. Calculated air volume (cfm) outside 264. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 264. ACH outside 2.9. ACH total 2.9. ACH Copy paste check (uses total or outside) 2.9.

Room 316. Diffuser air volume (cfm) 252. % Outside air 100. Calculated air volume (cfm) outside 252. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 252. ACH outside 3.2. ACH total 3.2. ACH Copy paste check (uses total or outside) 3.2.

Room 403. Diffuser air volume (cfm) 296. % Outside air 100. Calculated air volume (cfm) outside 296. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 296. ACH outside 3.8. ACH total 3.8. ACH Copy paste check (uses total or outside) 3.8.

Room 408. Diffuser air volume (cfm) 263. % Outside air 100. Calculated air volume (cfm) outside 263. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 263. ACH outside 2.7. ACH total 2.7. ACH Copy paste check (uses total or outside) 2.7.

Room 102. Diffuser air volume (cfm) 225. % Outside air 100. Calculated air volume (cfm) outside 225. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 225. ACH outside 1.2. ACH total 1.2. ACH Copy paste check (uses total or outside) 1.2.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Eliot John K 1 Commercial St.txt. Feel free to add Survey data. Eliot John K 1 Commercial St

CAB v 0.11 R -1

22:45:44 Start Time
22:45:44 End Time
0 Seconds

5.026003 cab pid: 1408582 httpd pid: error pid: