About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameEllison Parks ECC
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyCentral HVAC
12. Min ACH0.7
13. Max ACH1.6
14. Avg ACH1.1
15. eACH0
16. Filter MERV13
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft608.4
22. cuft6084
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 103. Diffuser air volume (cfm) 225. % Outside air 100. Calculated air volume (cfm) outside 225. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 225. ACH outside 1.2. ACH total 1.2. ACH Copy paste check (uses total or outside) 1.2.

Room 105. Diffuser air volume (cfm) 205. % Outside air 100. Calculated air volume (cfm) outside 205. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 205. ACH outside 1.1. ACH total 1.1. ACH Copy paste check (uses total or outside) 1.1.

Room 203. Diffuser air volume (cfm) 185. % Outside air 100. Calculated air volume (cfm) outside 185. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 185. ACH outside 1.6. ACH total 1.6. ACH Copy paste check (uses total or outside) 1.6.

Room 204. Diffuser air volume (cfm) 140. % Outside air 100. Calculated air volume (cfm) outside 140. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 140. ACH outside 0.7. ACH total 0.7. ACH Copy paste check (uses total or outside) 0.7.

Room 205. Diffuser air volume (cfm) 190. % Outside air 100. Calculated air volume (cfm) outside 190. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 190. ACH outside 1. ACH total 1. ACH Copy paste check (uses total or outside) 1.

Room 301. Diffuser air volume (cfm) 541. % Outside air 70. Calculated air volume (cfm) outside 379. Calculated air volume (cfm) return 162. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 517. ACH outside 3.7. ACH merv filter return air 1.3. ACH total 5. ACH Copy paste check (uses total or outside) 5.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Ellison Parks ECC.txt. Feel free to add Survey data. Ellison Parks ECC

CAB v 0.11 R -1