0. Space TypeBOS-School
1. Establishment NameEnglish High School
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyCentral HVAC
12. Min ACH4.8
13. Max ACH9.3
14. Avg ACH6.4
15. eACH0
16. Filter MERV---
17. Percent Outside Air69.8
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft772.6
22. cuft7726
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 321. Diffuser air volume (cfm) 530. % Outside air 70. Calculated air volume (cfm) outside 371. Calculated air volume (cfm) return 159. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 506. ACH outside 3.5. ACH merv filter return air 1.3. ACH total 4.8. ACH Copy paste check (uses total or outside) 4.8.

Room 420. Diffuser air volume (cfm) 573. % Outside air 70. Calculated air volume (cfm) outside 401. Calculated air volume (cfm) return 171. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 546. ACH outside 3.7. ACH merv filter return air 1.4. ACH total 5.1. ACH Copy paste check (uses total or outside) 5.1.

Room 442. Diffuser air volume (cfm) 1172. % Outside air 70. Calculated air volume (cfm) outside 820. Calculated air volume (cfm) return 352. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 1119. ACH outside 6.6. ACH merv filter return air 2.4. ACH total 9. ACH Copy paste check (uses total or outside) 9.

Room 507. Diffuser air volume (cfm) 627. % Outside air 70. Calculated air volume (cfm) outside 439. Calculated air volume (cfm) return 188. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 599. ACH outside 4.1. ACH merv filter return air 1.5. ACH total 5.6. ACH Copy paste check (uses total or outside) 5.6.

Room 536. Diffuser air volume (cfm) 975. % Outside air 70. Calculated air volume (cfm) outside 682. Calculated air volume (cfm) return 292. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 930. ACH outside 6.8. ACH merv filter return air 2.5. ACH total 9.3. ACH Copy paste check (uses total or outside) 9.3.

Room A343. Diffuser air volume (cfm) 740. % Outside air 100. Calculated air volume (cfm) outside 740. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 740. ACH outside 5.8. ACH total 5.8. ACH Copy paste check (uses total or outside) 5.8.