About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameFrederick Lilla G Middle
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyCentral HVAC
12. Min ACH2.9
13. Max ACH5.8
14. Avg ACH4
15. eACH0
16. Filter MERV---
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft609
22. cuft6090
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room B105. Diffuser air volume (cfm) 843. % Outside air 100. Calculated air volume (cfm) outside 843. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 843. ACH outside 2.9. ACH total 2.9. ACH Copy paste check (uses total or outside) 2.9.

Room B107. Diffuser air volume (cfm) 888. % Outside air 100. Calculated air volume (cfm) outside 888. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 888. ACH outside 3. ACH total 3. ACH Copy paste check (uses total or outside) 3.

Room B208. Diffuser air volume (cfm) 593. % Outside air 100. Calculated air volume (cfm) outside 593. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 593. ACH outside 4.1. ACH total 4.1. ACH Copy paste check (uses total or outside) 4.1.

Room B222. Diffuser air volume (cfm) 712. % Outside air 100. Calculated air volume (cfm) outside 712. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 712. ACH outside 5.5. ACH total 5.5. ACH Copy paste check (uses total or outside) 5.5.

Room B330. Diffuser air volume (cfm) 374. % Outside air 100. Calculated air volume (cfm) outside 374. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 374. ACH outside 2.9. ACH total 2.9. ACH Copy paste check (uses total or outside) 2.9.

Room 202. Diffuser air volume (cfm) 1087. % Outside air 100. Calculated air volume (cfm) outside 1087. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 1087. ACH outside 10.7. ACH total 10.7. ACH Copy paste check (uses total or outside) 10.7.