About Us | Contact Us |
0. Space Type | BOS-School |
1. Establishment Name | Greater Egleston High School |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Central HVAC |
12. Min ACH | 0 |
13. Max ACH | 10.8 |
14. Avg ACH | 7.6 |
15. eACH | 0 |
16. Filter MERV | --- |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 900 |
22. cuft | 9000 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 205. Diffuser air volume (cfm) 1262. % Outside air 100. Calculated air volume (cfm) outside 1262. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 1262. ACH outside 10.8. ACH total 10.8. ACH Copy paste check (uses total or outside) 10.8. Room 210. Diffuser air volume (cfm) Not Operating. % Outside air 100. Calculated air volume (cfm) outside 0. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 0. ACH outside 0. ACH total 0. ACH Copy paste check (uses total or outside) 0. Room 211. Diffuser air volume (cfm) 604. % Outside air 100. Calculated air volume (cfm) outside 604. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 604. ACH outside 7.6. ACH total 7.6. ACH Copy paste check (uses total or outside) 7.6. Room 215. Diffuser air volume (cfm) 857. % Outside air 100. Calculated air volume (cfm) outside 857. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 857. ACH outside 9.9. ACH total 9.9. ACH Copy paste check (uses total or outside) 9.9. Room 216. Diffuser air volume (cfm) 902. % Outside air 100. Calculated air volume (cfm) outside 902. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 902. ACH outside 6.7. ACH total 6.7. ACH Copy paste check (uses total or outside) 6.7. Room 101. Diffuser air volume (cfm) 375. % Outside air 100. Calculated air volume (cfm) outside 375. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 375. ACH outside 2.5. ACH total 2.5. |