About Us | Contact Us |
0. Space Type | BOS-School |
1. Establishment Name | Haynes Early Education Center |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Central HVAC |
12. Min ACH | 1.9 |
13. Max ACH | 4.5 |
14. Avg ACH | 3 |
15. eACH | 0 |
16. Filter MERV | 13 |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 10 |
21. sqft | 131.8 |
22. cuft | 1318 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 101. Diffuser air volume (cfm) 400. % Outside air 100. Calculated air volume (cfm) outside 400. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 400. ACH outside 2.7. ACH total 2.7. Room 104. Diffuser air volume (cfm) 470. % Outside air 100. Calculated air volume (cfm) outside 470. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 470. ACH outside 3.1. ACH total 3.1. Room 104. Diffuser air volume (cfm) 475. % Outside air 100. Calculated air volume (cfm) outside 475. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 475. ACH outside 3.2. ACH total 3.2. Room 201. Diffuser air volume (cfm) 660. % Outside air 100. Calculated air volume (cfm) outside 660. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 660. ACH outside 4.4. ACH total 4.4. Room 203. Diffuser air volume (cfm) 285. % Outside air 100. Calculated air volume (cfm) outside 285. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 285. ACH outside 1.9. ACH total 1.9. Room 203. Diffuser air volume (cfm) 300. % Outside air 100. Calculated air volume (cfm) outside 300. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 300. ACH outside 2. ACH total 2. Room 204. Diffuser air volume (cfm) 670. % Outside air 100. Calculated air volume (cfm) outside 670. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 670. ACH outside 4.5. ACH total 4.5. Room 302. Diffuser air volume (cfm) 450. % Outside air 100. Calculated air volume (cfm) outside 450. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 450. ACH outside 3. ACH total 3. Room 304. Diffuser air volume (cfm) 455. % Outside air 100. Calculated air volume (cfm) outside 455. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 455. ACH outside 3. ACH total 3. Room A-21. Diffuser air volume (cfm) 43. % Outside air 50. Calculated air volume (cfm) outside 22. Calculated air volume (cfm) return 21. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 40. ACH outside 1. ACH merv filter return air 0.8. ACH total 1.8. |