Building Data Report

0. Space TypeBOS-School
1. Establishment NameHaynes Early Education Center
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyCentral HVAC
12. Min ACH1.9
13. Max ACH4.5
14. Avg ACH3
15. eACH0
16. Filter MERV13
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms10
21. sqft131.8
22. cuft1318
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 101. Diffuser air volume (cfm) 400. % Outside air 100. Calculated air volume (cfm) outside 400. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 400. ACH outside 2.7. ACH total 2.7.

Room 104. Diffuser air volume (cfm) 470. % Outside air 100. Calculated air volume (cfm) outside 470. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 470. ACH outside 3.1. ACH total 3.1.

Room 104. Diffuser air volume (cfm) 475. % Outside air 100. Calculated air volume (cfm) outside 475. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 475. ACH outside 3.2. ACH total 3.2.

Room 201. Diffuser air volume (cfm) 660. % Outside air 100. Calculated air volume (cfm) outside 660. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 660. ACH outside 4.4. ACH total 4.4.

Room 203. Diffuser air volume (cfm) 285. % Outside air 100. Calculated air volume (cfm) outside 285. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 285. ACH outside 1.9. ACH total 1.9.

Room 203. Diffuser air volume (cfm) 300. % Outside air 100. Calculated air volume (cfm) outside 300. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 300. ACH outside 2. ACH total 2.

Room 204. Diffuser air volume (cfm) 670. % Outside air 100. Calculated air volume (cfm) outside 670. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 670. ACH outside 4.5. ACH total 4.5.

Room 302. Diffuser air volume (cfm) 450. % Outside air 100. Calculated air volume (cfm) outside 450. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 450. ACH outside 3. ACH total 3.

Room 304. Diffuser air volume (cfm) 455. % Outside air 100. Calculated air volume (cfm) outside 455. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 455. ACH outside 3. ACH total 3.

Room A-21. Diffuser air volume (cfm) 43. % Outside air 50. Calculated air volume (cfm) outside 22. Calculated air volume (cfm) return 21. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 40. ACH outside 1. ACH merv filter return air 0.8. ACH total 1.8.