About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameMadison Park Technical Vocational
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyCentral HVAC
12. Min ACH4.6
13. Max ACH12.3
14. Avg ACH7.8
15. eACH0
16. Filter MERV13
17. Percent Outside Air69.8
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1125
22. cuft11250
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 7-245. Diffuser air volume (cfm) 780. % Outside air 70. Calculated air volume (cfm) outside 546. Calculated air volume (cfm) return 234. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 745. ACH outside 4. ACH merv filter return air 1.5. ACH total 5.5.

Room 7-275. Diffuser air volume (cfm) 2601. % Outside air 70. Calculated air volume (cfm) outside 1821. Calculated air volume (cfm) return 780. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 2484. ACH outside 9. ACH merv filter return air 3.3. ACH total 12.3.

Room 7-341. Diffuser air volume (cfm) 2120. % Outside air 70. Calculated air volume (cfm) outside 1484. Calculated air volume (cfm) return 636. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 2025. ACH outside 7.4. ACH merv filter return air 2.7. ACH total 10.1.

Room 7-365. Diffuser air volume (cfm) 511. % Outside air 70. Calculated air volume (cfm) outside 358. Calculated air volume (cfm) return 153. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 488. ACH outside 3.4. ACH merv filter return air 1.2. ACH total 4.6.

Room 7-384. Diffuser air volume (cfm) 1255. % Outside air 70. Calculated air volume (cfm) outside 879. Calculated air volume (cfm) return 376. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 1199. ACH outside 5.7. ACH merv filter return air 2.1. ACH total 7.8.

Room 123. Diffuser air volume (cfm) 573. % Outside air 70. Calculated air volume (cfm) outside 401. Calculated air volume (cfm) return 172. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 547. ACH outside 2.1. ACH merv filter return air 0.8. ACH total 2.9.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Madison Park Technical Vocational.txt. Feel free to add Survey data. Madison Park Technical Vocational

CAB v 0.11 R -1

10:44:28 Start Time
10:44:28 End Time
0 Seconds