About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameMattahunt Elementary School
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyCentral HVAC
12. Min ACH2.9
13. Max ACH7.8
14. Avg ACH4.9
15. eACH0
16. Filter MERV---
17. Percent Outside Air69.5
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft882
22. cuft8820
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 215. Diffuser air volume (cfm) 567. % Outside air 70. Calculated air volume (cfm) outside 397. Calculated air volume (cfm) return 170. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 542. ACH outside 3. ACH merv filter return air 1.1. ACH total 4.1.

Room 231. Diffuser air volume (cfm) 535. % Outside air 70. Calculated air volume (cfm) outside 374. Calculated air volume (cfm) return 160. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 510. ACH outside 2.8. ACH merv filter return air 0.8. ACH total 3.6.

Room 317. Diffuser air volume (cfm) 1072. % Outside air 70. Calculated air volume (cfm) outside 750. Calculated air volume (cfm) return 322. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 1024. ACH outside 5.7. ACH merv filter return air 2.1. ACH total 7.8.

Room 318. Diffuser air volume (cfm) 873. % Outside air 70. Calculated air volume (cfm) outside 611. Calculated air volume (cfm) return 262. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 834. ACH outside 4.7. ACH merv filter return air 1.7. ACH total 6.4.

Room 334. Diffuser air volume (cfm) 711. % Outside air 70. Calculated air volume (cfm) outside 498. Calculated air volume (cfm) return 213. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 679. ACH outside 3.8. ACH merv filter return air 1.4. ACH total 5.2.

Room A304. Diffuser air volume (cfm) 740. % Outside air 100. Calculated air volume (cfm) outside 740. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 740. ACH outside 5. ACH total 5.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Mattahunt Elementary School.txt. Feel free to add Survey data. Mattahunt Elementary School

CAB v 0.11 R -1

04:04:46 Start Time
04:04:46 End Time
0 Seconds

5.026003 cab pid: 563408 httpd pid: error pid: