About Us | Contact Us |
0. Space Type | BOS-School |
1. Establishment Name | Mildred Avenue K 8 |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Central HVAC |
12. Min ACH | 3.3 |
13. Max ACH | 5 |
14. Avg ACH | 3.9 |
15. eACH | 0 |
16. Filter MERV | --- |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 1000 |
22. cuft | 10000 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room B105. Diffuser air volume (cfm) 682. % Outside air 100. Calculated air volume (cfm) outside 682. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 682. ACH outside 3.4. ACH total 3.4. Room B117. Diffuser air volume (cfm) 682. % Outside air 100. Calculated air volume (cfm) outside 682. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 682. ACH outside 3.6. ACH total 3.6. Room B207. Diffuser air volume (cfm) 480. % Outside air 100. Calculated air volume (cfm) outside 480. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 480. ACH outside 3.3. ACH total 3.3. Room B216. Diffuser air volume (cfm) 525. % Outside air 100. Calculated air volume (cfm) outside 525. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 525. ACH outside 3.6. ACH total 3.6. Room B323. Diffuser air volume (cfm) 655. % Outside air 100. Calculated air volume (cfm) outside 655. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 655. ACH outside 4.5. ACH total 4.5. Room 203. Diffuser air volume (cfm) 395. % Outside air 100. Calculated air volume (cfm) outside 395. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 395. ACH outside 2.4. ACH total 2.4. |