0. Space Type | BOS-School |
1. Establishment Name | Mission Hill K 8 |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Central HVAC |
12. Min ACH | 2.3 |
13. Max ACH | 2.9 |
14. Avg ACH | 2.6 |
15. eACH | 0 |
16. Filter MERV | --- |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 540 |
22. cuft | 5400 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 204. Diffuser air volume (cfm) 350. % Outside air 100. Calculated air volume (cfm) outside 350. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 350. ACH outside 2.5. ACH total 2.5. Room 205. Diffuser air volume (cfm) 320. % Outside air 100. Calculated air volume (cfm) outside 320. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 320. ACH outside 2.3. ACH total 2.3. Room 213. Diffuser air volume (cfm) 390. % Outside air 100. Calculated air volume (cfm) outside 390. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 390. ACH outside 2.9. ACH total 2.9. Room 214. Diffuser air volume (cfm) 395. % Outside air 100. Calculated air volume (cfm) outside 395. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 395. ACH outside 2.9. ACH total 2.9. Room 217. Diffuser air volume (cfm) 370. % Outside air 100. Calculated air volume (cfm) outside 370. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 370. ACH outside 2.8. ACH total 2.8. Room 101. Diffuser air volume (cfm) 312. % Outside air 100. Calculated air volume (cfm) outside 312. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 312. ACH outside 3.5. ACH total 3.5. |