About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameMuniz Margarite Academy
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyCentral HVAC
12. Min ACH1.8
13. Max ACH9.9
14. Avg ACH4.1
15. eACH0
16. Filter MERV13
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft579.6
22. cuft5796
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 105. Diffuser air volume (cfm) 890. % Outside air 100. Calculated air volume (cfm) outside 890. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 890. ACH outside 9.9. ACH total 9.9.

Room 108. Diffuser air volume (cfm) 394. % Outside air 100. Calculated air volume (cfm) outside 394. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 394. ACH outside 2.1. ACH total 2.1.

Room 306. Diffuser air volume (cfm) 290. % Outside air 100. Calculated air volume (cfm) outside 290. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 290. ACH outside 3.9. ACH total 3.9.

Room 308. Diffuser air volume (cfm) 300. % Outside air 100. Calculated air volume (cfm) outside 300. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 300. ACH outside 3.6. ACH total 3.6.

Room 315. Diffuser air volume (cfm) 250. % Outside air 100. Calculated air volume (cfm) outside 250. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 250. ACH outside 1.8. ACH total 1.8.

Room 108. Diffuser air volume (cfm) 262. % Outside air 50. Calculated air volume (cfm) outside 131. Calculated air volume (cfm) return 131. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 242. ACH outside 1.4. ACH merv filter return air 1.15. ACH total 2.55.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Muniz Margarite Academy.txt. Feel free to add Survey data. Muniz Margarite Academy

CAB v 0.11 R -1

23:26:35 Start Time
23:26:35 End Time
0 Seconds

5.026003 cab pid: 3448525 httpd pid: error pid: