About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameOrchard Gardens K 8
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyCentral HVAC
12. Min ACH3
13. Max ACH4.2
14. Avg ACH3.8
15. eACH0
16. Filter MERV13
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft430
22. cuft4300
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 151. Diffuser air volume (cfm) 500. % Outside air 100. Calculated air volume (cfm) outside 500. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 500. ACH outside 4.1. ACH total 4.1.

Room 152. Diffuser air volume (cfm) 622. % Outside air 100. Calculated air volume (cfm) outside 622. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 622. ACH outside 3.5. ACH total 3.5.

Room 217. Diffuser air volume (cfm) 555. % Outside air 100. Calculated air volume (cfm) outside 555. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 555. ACH outside 4.1. ACH total 4.1.

Room 218. Diffuser air volume (cfm) 540. % Outside air 100. Calculated air volume (cfm) outside 540. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 540. ACH outside 4.2. ACH total 4.2.

Room 236. Diffuser air volume (cfm) 310. % Outside air 100. Calculated air volume (cfm) outside 310. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 310. ACH outside 3. ACH total 3.

Room 102. Diffuser air volume (cfm) 692. % Outside air 70. Calculated air volume (cfm) outside 484. Calculated air volume (cfm) return 208. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 661. ACH outside 6.8. ACH merv filter return air 2.5. ACH total 9.3.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Orchard Gardens K 8.txt. Feel free to add Survey data. Orchard Gardens K 8

CAB v 0.11 R -1

04:38:26 Start Time
04:38:26 End Time
0 Seconds

5.026003 cab pid: 583341 httpd pid: error pid: