About Us | Contact Us |
0. Space Type | BOS-School |
1. Establishment Name | Quincy Josiah Elementary |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Central HVAC |
12. Min ACH | 9.3 |
13. Max ACH | 17.9 |
14. Avg ACH | 13.4 |
15. eACH | 0 |
16. Filter MERV | --- |
17. Percent Outside Air | 69.3 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 817.4 |
22. cuft | 8174 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 103. Diffuser air volume (cfm) 932. % Outside air 70. Calculated air volume (cfm) outside 652. Calculated air volume (cfm) return 280. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 890. ACH outside 6.9. ACH merv filter return air 3. ACH total 9.9. Room 206. Diffuser air volume (cfm) 2544. % Outside air 70. Calculated air volume (cfm) outside 1781. Calculated air volume (cfm) return 763. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 2430. ACH outside 10.4. ACH merv filter return air 3.8. ACH total 14.2. Room 216. Diffuser air volume (cfm) 2072. % Outside air 70. Calculated air volume (cfm) outside 1450. Calculated air volume (cfm) return 622. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 1979. ACH outside 12. ACH merv filter return air 4.4. ACH total 16.4. Room 307. Diffuser air volume (cfm) 856. % Outside air 70. Calculated air volume (cfm) outside 599. Calculated air volume (cfm) return 257. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 817. ACH outside 13.1. ACH merv filter return air 4.8. ACH total 17.9. Room 317. Diffuser air volume (cfm) 2567. % Outside air 70. Calculated air volume (cfm) outside 1797. Calculated air volume (cfm) return 770. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 2452. ACH outside 9.7. ACH merv filter return air 3.5. ACH total 13.2. Room 102. Diffuser air volume (cfm) 360. % Outside air 100. Calculated air volume (cfm) outside 360. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 360. ACH outside 2.6. ACH total 2.6. |