0. Space TypeBOS-School
1. Establishment NameQuincy Josiah Modular
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyCentral HVAC
12. Min ACH2.6
13. Max ACH3.3
14. Avg ACH2.8
15. eACH0
16. Filter MERV85
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft911.7
22. cuft9117
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 104. Diffuser air volume (cfm) 380. % Outside air 100. Calculated air volume (cfm) outside 380. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 380. ACH outside 2.8. ACH total 2.8.

Room 105. Diffuser air volume (cfm) 450. % Outside air 100. Calculated air volume (cfm) outside 450. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 450. ACH outside 3.3. ACH total 3.3.

Room 200. Diffuser air volume (cfm) 450. % Outside air 100. Calculated air volume (cfm) outside 450. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 450. ACH outside 2.6. ACH total 2.6.

Room 203. Diffuser air volume (cfm) 300. % Outside air 100. Calculated air volume (cfm) outside 300. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 300. ACH outside 3.3. ACH total 3.3.

Room 204. Diffuser air volume (cfm) 250. % Outside air 100. Calculated air volume (cfm) outside 250. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 250. ACH outside 2.7. ACH total 2.7.

Room 133. Diffuser air volume (cfm) 1043. % Outside air 70. Calculated air volume (cfm) outside 730. Calculated air volume (cfm) return 313. Filter merv rating 85. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 996. ACH outside 4.8. ACH merv filter return air 1.8. ACH total 6.6.