Building Data Report

0. Space TypeBOS-School
1. Establishment NameHarvard Kent Elem
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyUnivent Central HVAC
12. Min ACH7
13. Max ACH11.6
14. Avg ACH10.1
15. eACH0
16. Filter MERV
17. Percent Outside Air78.5
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft660
22. cuft6600
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 209. % Outside air 88. Calculated air volume (cfm) outside 800. Calculated air volume (cfm) return 105. Combined air volume (cfm) 905. ACH outside 10.3. ACH merv filter return air 1.3. ACH total 11.6. ACH Copy paste check (uses total or outside) 10.3.

Room 306. % Outside air 72. Calculated air volume (cfm) outside 885. Calculated air volume (cfm) return 350. Combined air volume (cfm) 1235. ACH outside 7.0. ACH merv filter return air 2.8. ACH total 9.8. ACH Copy paste check (uses total or outside) 7.

Room 302. % Outside air 77. Calculated air volume (cfm) outside 950. Calculated air volume (cfm) return 290. Combined air volume (cfm) 1240. ACH outside 8.1. ACH merv filter return air 2.5. ACH total 10.6. ACH Copy paste check (uses total or outside) 8.1.

Room 407. % Outside air 77. Calculated air volume (cfm) outside 950. Calculated air volume (cfm) return 290. Combined air volume (cfm) 1240. ACH outside 8.4. ACH merv filter return air 2.6. ACH total 10.9. ACH Copy paste check (uses total or outside) 8.4.

Room 403. % Outside air 78. Calculated air volume (cfm) outside 940. Calculated air volume (cfm) return 270. Combined air volume (cfm) 1210. ACH outside 8.3. ACH merv filter return air 2.4. ACH total 10.7. ACH Copy paste check (uses total or outside) 8.3.

Room 307. % Outside air 63. Calculated air volume (cfm) outside 450. Calculated air volume (cfm) return 260. Combined air volume (cfm) 710. ACH outside 4.1. ACH merv filter return air 2.4. ACH total 6.5. ACH Copy paste check (uses total or outside) 4.1.