0. Space Type | BOS-School |
1. Establishment Name | Harvard Kent Elem |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Univent Central HVAC |
12. Min ACH | 7 |
13. Max ACH | 11.6 |
14. Avg ACH | 10.1 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 78.5 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 660 |
22. cuft | 6600 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 209. % Outside air 88. Calculated air volume (cfm) outside 800. Calculated air volume (cfm) return 105. Combined air volume (cfm) 905. ACH outside 10.3. ACH merv filter return air 1.3. ACH total 11.6. ACH Copy paste check (uses total or outside) 10.3. Room 306. % Outside air 72. Calculated air volume (cfm) outside 885. Calculated air volume (cfm) return 350. Combined air volume (cfm) 1235. ACH outside 7.0. ACH merv filter return air 2.8. ACH total 9.8. ACH Copy paste check (uses total or outside) 7. Room 302. % Outside air 77. Calculated air volume (cfm) outside 950. Calculated air volume (cfm) return 290. Combined air volume (cfm) 1240. ACH outside 8.1. ACH merv filter return air 2.5. ACH total 10.6. ACH Copy paste check (uses total or outside) 8.1. Room 407. % Outside air 77. Calculated air volume (cfm) outside 950. Calculated air volume (cfm) return 290. Combined air volume (cfm) 1240. ACH outside 8.4. ACH merv filter return air 2.6. ACH total 10.9. ACH Copy paste check (uses total or outside) 8.4. Room 403. % Outside air 78. Calculated air volume (cfm) outside 940. Calculated air volume (cfm) return 270. Combined air volume (cfm) 1210. ACH outside 8.3. ACH merv filter return air 2.4. ACH total 10.7. ACH Copy paste check (uses total or outside) 8.3. Room 307. % Outside air 63. Calculated air volume (cfm) outside 450. Calculated air volume (cfm) return 260. Combined air volume (cfm) 710. ACH outside 4.1. ACH merv filter return air 2.4. ACH total 6.5. ACH Copy paste check (uses total or outside) 4.1. |