0. Space TypeBOS-School
1. Establishment NameHennigan James W K 8
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyUnivent Central HVAC
12. Min ACH3.5
13. Max ACH6.5
14. Avg ACH4.9
15. eACH0
16. Filter MERV
17. Percent Outside Air70
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft891
22. cuft8910
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 313. % Outside air 83. Calculated air volume (cfm) outside 511. Calculated air volume (cfm) return 104. Combined air volume (cfm) 615. ACH outside 4.4. ACH merv filter return air 0.9. ACH total 5.2. ACH Copy paste check (uses total or outside) 4.4.

Room 401. % Outside air 68. Calculated air volume (cfm) outside 530. Calculated air volume (cfm) return 250. Combined air volume (cfm) 780. ACH outside 3.9. ACH merv filter return air 1.8. ACH total 5.7. ACH Copy paste check (uses total or outside) 3.

Room 404. % Outside air 69. Calculated air volume (cfm) outside 410. Calculated air volume (cfm) return 180. Combined air volume (cfm) 590. ACH outside 3.0. ACH merv filter return air 1.3. ACH total 4.3. ACH Copy paste check (uses total or outside) 3.

Room 419. % Outside air 77. Calculated air volume (cfm) outside 360. Calculated air volume (cfm) return 110. Combined air volume (cfm) 470. ACH outside 2.6. ACH merv filter return air 0.8. ACH total 3.5. ACH Copy paste check (uses total or outside) 2.6.

Room 301. % Outside air 63. Calculated air volume (cfm) outside 375. Calculated air volume (cfm) return 225. Combined air volume (cfm) 600. ACH outside 2.9. ACH merv filter return air 1.7. ACH total 4.6. ACH Copy paste check (uses total or outside) 2.9.

Room 104. % Outside air 65. Calculated air volume (cfm) outside 305. Calculated air volume (cfm) return 165. Combined air volume (cfm) 470. ACH outside 2.1. ACH merv filter return air 1.1. ACH total 3.2. ACH Copy paste check (uses total or outside) 2.1.