0. Space Type | BOS-School |
1. Establishment Name | Hennigan James W K 8 |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Univent Central HVAC |
12. Min ACH | 3.5 |
13. Max ACH | 6.5 |
14. Avg ACH | 4.9 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 70 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 891 |
22. cuft | 8910 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 313. % Outside air 83. Calculated air volume (cfm) outside 511. Calculated air volume (cfm) return 104. Combined air volume (cfm) 615. ACH outside 4.4. ACH merv filter return air 0.9. ACH total 5.2. ACH Copy paste check (uses total or outside) 4.4. Room 401. % Outside air 68. Calculated air volume (cfm) outside 530. Calculated air volume (cfm) return 250. Combined air volume (cfm) 780. ACH outside 3.9. ACH merv filter return air 1.8. ACH total 5.7. ACH Copy paste check (uses total or outside) 3. Room 404. % Outside air 69. Calculated air volume (cfm) outside 410. Calculated air volume (cfm) return 180. Combined air volume (cfm) 590. ACH outside 3.0. ACH merv filter return air 1.3. ACH total 4.3. ACH Copy paste check (uses total or outside) 3. Room 419. % Outside air 77. Calculated air volume (cfm) outside 360. Calculated air volume (cfm) return 110. Combined air volume (cfm) 470. ACH outside 2.6. ACH merv filter return air 0.8. ACH total 3.5. ACH Copy paste check (uses total or outside) 2.6. Room 301. % Outside air 63. Calculated air volume (cfm) outside 375. Calculated air volume (cfm) return 225. Combined air volume (cfm) 600. ACH outside 2.9. ACH merv filter return air 1.7. ACH total 4.6. ACH Copy paste check (uses total or outside) 2.9. Room 104. % Outside air 65. Calculated air volume (cfm) outside 305. Calculated air volume (cfm) return 165. Combined air volume (cfm) 470. ACH outside 2.1. ACH merv filter return air 1.1. ACH total 3.2. ACH Copy paste check (uses total or outside) 2.1. |