About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameO Bryant Sch of Math Sci
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyUnivent Central HVAC
12. Min ACH1.9
13. Max ACH7.2
14. Avg ACH4.1
15. eACH0
16. Filter MERV
17. Percent Outside Air50.5
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms4
21. sqft886.6
22. cuft8866
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 3-108. % Outside air 45. Calculated air volume (cfm) outside 205. Calculated air volume (cfm) return 255. Combined air volume (cfm) 460. ACH outside 1.3. ACH merv filter return air 1.7. ACH total 3.0. ACH Copy paste check (uses total or outside) 1.3.

Room 3-116. % Outside air 57. Calculated air volume (cfm) outside 310. Calculated air volume (cfm) return 295. Combined air volume (cfm) 685. ACH outside 2.0. ACH merv filter return air 1.9. ACH total 4.4. ACH Copy paste check (uses total or outside) 2.5.

Room 3-223. % Outside air 61. Calculated air volume (cfm) outside 445. Calculated air volume (cfm) return 290. Combined air volume (cfm) 735. ACH outside 4.3. ACH merv filter return air 2.8. ACH total 7.2. ACH Copy paste check (uses total or outside) 4.3.

Room 125. % Outside air 82. Calculated air volume (cfm) outside 454. Calculated air volume (cfm) return 100. Combined air volume (cfm) 554. ACH outside 3.1. ACH merv filter return air 0.7. ACH total 3.7. ACH Copy paste check (uses total or outside) 3.1.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/O Bryant Sch of Math Sci.txt. Feel free to add Survey data. O Bryant Sch of Math Sci

CAB v 0.11 R -1

21:52:38 Start Time
21:52:38 End Time
0 Seconds

5.026003 cab pid: 291382 httpd pid: error pid: