About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameOhrenberger William School
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyUnivent Central HVAC
12. Min ACH2.1
13. Max ACH3.7
14. Avg ACH2.7
15. eACH0
16. Filter MERV
17. Percent Outside Air60.3
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft869.4
22. cuft8694
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 101. % Outside air 49. Calculated air volume (cfm) outside 262. Calculated air volume (cfm) return 275. Combined air volume (cfm) 537. ACH outside 1.5. ACH merv filter return air 1.5. ACH total 3.0. ACH Copy paste check (uses total or outside) 1.4.

Room 118. % Outside air 64. Calculated air volume (cfm) outside 395. Calculated air volume (cfm) return 220. Combined air volume (cfm) 615. ACH outside 1.6. ACH merv filter return air 0.9. ACH total 2.5. ACH Copy paste check (uses total or outside) 1.6.

Room 214. % Outside air 66. Calculated air volume (cfm) outside 278. Calculated air volume (cfm) return 142. Combined air volume (cfm) 420. ACH outside 1.5. ACH merv filter return air 0.8. ACH total 2.3. ACH Copy paste check (uses total or outside) 1.5.

Room 201. % Outside air 56. Calculated air volume (cfm) outside 225. Calculated air volume (cfm) return 175. Combined air volume (cfm) 400. ACH outside 1.2. ACH merv filter return air 0.9. ACH total 2.1. ACH Copy paste check (uses total or outside) 1.2.

Room 236. % Outside air 48. Calculated air volume (cfm) outside 263. Calculated air volume (cfm) return 289. Combined air volume (cfm) 552. ACH outside 1.4. ACH merv filter return air 1.5. ACH total 2.9. ACH Copy paste check (uses total or outside) 1.4.

Room 200. % Outside air 62. Calculated air volume (cfm) outside 687. Calculated air volume (cfm) return 425. Combined air volume (cfm) 1112. ACH outside 4.7. ACH merv filter return air 2.9. ACH total 7.7. ACH Copy paste check (uses total or outside) 4.7.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Ohrenberger William School.txt. Feel free to add Survey data. Ohrenberger William School

CAB v 0.11 R -1

12:16:47 Start Time
12:16:47 End Time
0 Seconds

5.026003 cab pid: 4034734 httpd pid: error pid: