Building Data Report

0. Space TypeBOS-School
1. Establishment NameTynan Jospeh P Elem
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyUnivent Central HVAC
12. Min ACH4.9
13. Max ACH8
14. Avg ACH6.6
15. eACH0
16. Filter MERV
17. Percent Outside Air67.2
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms5
21. sqft1094.4
22. cuft10944
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 225. % Outside air 76. Calculated air volume (cfm) outside 618. Calculated air volume (cfm) return 200. Combined air volume (cfm) 818. ACH outside 5.6. ACH merv filter return air 1.8. ACH total 7.4. ACH Copy paste check (uses total or outside) 5.6.

Room 218. % Outside air 79. Calculated air volume (cfm) outside 587. Calculated air volume (cfm) return 160. Combined air volume (cfm) 747. ACH outside 4.3. ACH merv filter return air 1.2. ACH total 5.4. ACH Copy paste check (uses total or outside) 4.3.

Room 129. % Outside air 73. Calculated air volume (cfm) outside 618. Calculated air volume (cfm) return 232. Combined air volume (cfm) 850. ACH outside 3.6. ACH merv filter return air 1.3. ACH total 4.9. ACH Copy paste check (uses total or outside) 3.6.

Room 116. % Outside air 51. Calculated air volume (cfm) outside 714. Calculated air volume (cfm) return 694. Combined air volume (cfm) 1408. ACH outside 4.0. ACH merv filter return air 3.9. ACH total 8.0. ACH Copy paste check (uses total or outside) 4.

Room 115C. % Outside air 51. Calculated air volume (cfm) outside 335. Calculated air volume (cfm) return 320. Combined air volume (cfm) 655. ACH outside 1.8. ACH merv filter return air 1.8. ACH total 3.6. ACH Copy paste check (uses total or outside) 1.8.