0. Space TypeBOS-School
1. Establishment NameUP Academy Dorchester
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyUnivent Central HVAC
12. Min ACH3.6
13. Max ACH7.6
14. Avg ACH5.6
15. eACH0
16. Filter MERV
17. Percent Outside Air71.5
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft704
22. cuft7040
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 108. % Outside air 80. Calculated air volume (cfm) outside 465. Calculated air volume (cfm) return 115. Combined air volume (cfm) 580. ACH outside 4.3. ACH merv filter return air 1.1. ACH total 5.4. ACH Copy paste check (uses total or outside) 4.3.

Room 205. % Outside air 77. Calculated air volume (cfm) outside 610. Calculated air volume (cfm) return 185. Combined air volume (cfm) 790. ACH outside 4.7. ACH merv filter return air 1.4. ACH total 6.1. ACH Copy paste check (uses total or outside) 4.7.

Room 212. % Outside air 78. Calculated air volume (cfm) outside 800. Calculated air volume (cfm) return 220. Combined air volume (cfm) 1020. ACH outside 6.0. ACH merv filter return air 1.6. ACH total 7.6. ACH Copy paste check (uses total or outside) 6.

Room 312. % Outside air 74. Calculated air volume (cfm) outside 590. Calculated air volume (cfm) return 210. Combined air volume (cfm) 800. ACH outside 4.4. ACH merv filter return air 1.6. ACH total 6.0. ACH Copy paste check (uses total or outside) 4.4.

Room 309. % Outside air 71. Calculated air volume (cfm) outside 500. Calculated air volume (cfm) return 200. Combined air volume (cfm) 700. ACH outside 3.7. ACH merv filter return air 1.5. ACH total 5.2. ACH Copy paste check (uses total or outside) 3.7.

Room 116. % Outside air 63. Calculated air volume (cfm) outside 440. Calculated air volume (cfm) return 260. Combined air volume (cfm) 700. ACH outside 3.8. ACH merv filter return air 2.2. ACH total 6.0. ACH Copy paste check (uses total or outside) 3.8.