0. Space TypeBOS-School
1. Establishment NameWest Zone ELC Hennigan
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyTechnology
12. Min ACH4.3
13. Max ACH6.7
14. Avg ACH5.3
15. eACH0
16. Filter MERVFILTER MERV RATING
17. Percent Outside Air69
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft0
22. cuftCLASSROOM VOLUME (FT3 )
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 114. % Outside air 63. Calculated air volume (cfm) outside 360. Calculated air volume (cfm) return 210. Combined air volume (cfm) 570. ACH outside 3.1. ACH merv filter return air 1.8. ACH total 4.9. ACH Copy paste check (uses total or outside) 3.1.

Room 110. % Outside air 78. Calculated air volume (cfm) outside 620. Calculated air volume (cfm) return 170. Combined air volume (cfm) 790. ACH outside 5.3. ACH merv filter return air 1.4. ACH total 6.7. ACH Copy paste check (uses total or outside) 5.3.

Room 106. % Outside air 77. Calculated air volume (cfm) outside 592. Calculated air volume (cfm) return 158. Combined air volume (cfm) 700. ACH outside 5.0. ACH merv filter return air 1.3. ACH total 6.0. ACH Copy paste check (uses total or outside) 4.6.

Room 103. % Outside air 52. Calculated air volume (cfm) outside 260. Calculated air volume (cfm) return 240. Combined air volume (cfm) 500. ACH outside 2.2. ACH merv filter return air 2.0. ACH total 4.3. ACH Copy paste check (uses total or outside) 2.2.

Room 101. % Outside air 81. Calculated air volume (cfm) outside 405. Calculated air volume (cfm) return 95. Combined air volume (cfm) 500. ACH outside 3.5. ACH merv filter return air 0.8. ACH total 4.3. ACH Copy paste check (uses total or outside) 3.5.

Room ROOM. Diffuser air volume (cfm) DIFFUSER AIR VOLUME (CFM). % Outside air % OUTSIDE AIR . Calculated air volume (cfm) outside CALCULATED AIR VOLUME (CFM) OUTSIDE. Calculated air volume (cfm) return CALCULATED AIR VOLUME (CFM) RETURN. Filter merv rating FILTER MERV RATING . Filter efficiency (decimal) FILTER EFFICIENCY (DECIMAL). Combined air volume (cfm) COMBINED AIR VOLUME (CFM). ACH outside AIR CHANGES PER HOUR (FRESH AIR). ACH merv filter return air AIR CHANGES PER HOUR (RETURN AIR). ACH total AIR CHANGES PER HOUR (TOTAL). ACH Copy paste check (uses total or outside) copy paste check (uses total).