0. Space TypeBOS-School
1. Establishment NameBoston Community Leadership Acad
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited HVAC
12. Min ACH1.8
13. Max ACH3.3
14. Avg ACH2.5
15. eACH0
16. Filter MERV---
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft900
22. cuft9000
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 114. Diffuser air volume (cfm) 469. % Outside air 100. Calculated air volume (cfm) outside 469. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 469. ACH outside 3.3. ACH merv filter return air 0.0. ACH total 3.3. ACH Copy paste check (uses total or outside) 3.1.

Room 117. Diffuser air volume (cfm) 419. % Outside air 100. Calculated air volume (cfm) outside 419. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 419. ACH outside 3.0. ACH merv filter return air 0.0. ACH total 3.0. ACH Copy paste check (uses total or outside) 3.

Room 14. Diffuser air volume (cfm) 217. % Outside air 100. Calculated air volume (cfm) outside 217. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 217. ACH outside 1.8. ACH merv filter return air 0.0. ACH total 1.8. ACH Copy paste check (uses total or outside) 1.8.

Room 211. Diffuser air volume (cfm) 288. % Outside air 100. Calculated air volume (cfm) outside 288. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 288. ACH outside 1.9. ACH merv filter return air 0.0. ACH total 1.9. ACH Copy paste check (uses total or outside) 1.9.

Room 216. Diffuser air volume (cfm) 495. % Outside air 100. Calculated air volume (cfm) outside 495. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 495. ACH outside 3.3. ACH merv filter return air 0.0. ACH total 3.3. ACH Copy paste check (uses total or outside) 3.3.

Room 103. Diffuser air volume (cfm) 204. % Outside air 100. Calculated air volume (cfm) outside 204. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 204. ACH outside 1.4. ACH merv filter return air 0.0. ACH total 1.4. ACH Copy paste check (uses total or outside) 1.4.