0. Space TypeBOS-School
1. Establishment NameBoston Latin School
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited HVAC
12. Min ACH1.1
13. Max ACH5.4
14. Avg ACH2.1
15. eACH0
16. Filter MERV---
17. Percent Outside Air94.8
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1122.4
22. cuft11224
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 137. Diffuser air volume (cfm) 215. % Outside air 100. Calculated air volume (cfm) outside 215. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 215. ACH outside 1.3. ACH merv filter return air 0.0. ACH total 1.3. ACH Copy paste check (uses total or outside) 1.3.

Room 221. Diffuser air volume (cfm) 270. % Outside air 100. Calculated air volume (cfm) outside 270. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 270. ACH outside 1.7. ACH merv filter return air 0.0. ACH total 1.7. ACH Copy paste check (uses total or outside) 1.7.

Room 234. Diffuser air volume (cfm) 260. % Outside air 100. Calculated air volume (cfm) outside 260. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 260. ACH outside 1.7. ACH merv filter return air 0.0. ACH total 1.7. ACH Copy paste check (uses total or outside) 1.7.

Room 303. Diffuser air volume (cfm) 245. % Outside air 100. Calculated air volume (cfm) outside 245. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 245. ACH outside 1.6. ACH merv filter return air 0.0. ACH total 1.6. ACH Copy paste check (uses total or outside) 1.6.

Room 514. Diffuser air volume (cfm) 1219. % Outside air 70. Calculated air volume (cfm) outside 853. Calculated air volume (cfm) return 366. Filter merv rating 85. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 1164. ACH outside 3.9. ACH merv filter return air 1.7. ACH total 5.4. ACH Copy paste check (uses total or outside) 5.3.

Room 101. Diffuser air volume (cfm) 299. % Outside air 100. Calculated air volume (cfm) outside 299. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 299. ACH outside 1.6. ACH merv filter return air 0.0. ACH total 1.6. ACH Copy paste check (uses total or outside) 1.6.