About Us | Contact Us |
0. Space Type | BOS-School |
1. Establishment Name | Boston Teachers Union K 8 School |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited HVAC |
12. Min ACH | 1.6 |
13. Max ACH | 3.7 |
14. Avg ACH | 2.6 |
15. eACH | 0 |
16. Filter MERV | 13 |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 4 |
21. sqft | 1011 |
22. cuft | 10110 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 105. Diffuser air volume (cfm) 516. % Outside air 100. Calculated air volume (cfm) outside 516. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 516. ACH outside 3.4. ACH merv filter return air 0.0. ACH total 3.4. ACH Copy paste check (uses total or outside) 3.4. Room 208. Diffuser air volume (cfm) 274. % Outside air 100. Calculated air volume (cfm) outside 274. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 274. ACH outside 1.8. ACH merv filter return air 0.0. ACH total 1.8. ACH Copy paste check (uses total or outside) 1.8. Room 212. Diffuser air volume (cfm) 524. % Outside air 100. Calculated air volume (cfm) outside 524. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 524. ACH outside 3.7. ACH merv filter return air 0.0. ACH total 3.7. ACH Copy paste check (uses total or outside) 3.7. Room 109. Diffuser air volume (cfm) 770. % Outside air 70. Calculated air volume (cfm) outside 539. Calculated air volume (cfm) return 231. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 735. ACH outside 3.2. ACH merv filter return air 1.4. ACH total 4.4. ACH Copy paste check (uses total or outside) 4.4. |