About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameDudley St Neighborhood Charter
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited HVAC
12. Min ACH3.9
13. Max ACH4.4
14. Avg ACH4.1
15. eACH0
16. Filter MERV---
17. Percent Outside Air69.5
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms4
21. sqft1
22. cuft10,626
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 110. Diffuser air volume (cfm) 824. % Outside air 70. Calculated air volume (cfm) outside 577. Calculated air volume (cfm) return 247. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 787. ACH outside 3.0. ACH merv filter return air 1.3. ACH total 4.0. ACH Copy paste check (uses total or outside) 4.1.

Room 111. Diffuser air volume (cfm) 802. % Outside air 70. Calculated air volume (cfm) outside 561. Calculated air volume (cfm) return 241. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 766. ACH outside 2.8. ACH merv filter return air 1.2. ACH total 3.9. ACH Copy paste check (uses total or outside) 3.8.

Room 112. Diffuser air volume (cfm) 913. % Outside air 70. Calculated air volume (cfm) outside 639. Calculated air volume (cfm) return 274. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 872. ACH outside 3.2. ACH merv filter return air 1.4. ACH total 4.4. ACH Copy paste check (uses total or outside) 4.4.

Room 104. Diffuser air volume (cfm) 720. % Outside air 100. Calculated air volume (cfm) outside 720. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 720. ACH outside 4.1. ACH merv filter return air 0.0. ACH total 4.1. ACH Copy paste check (uses total or outside) 4.1.