0. Space Type | BOS-School |
1. Establishment Name | East Boston Early Education Center |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited HVAC |
12. Min ACH | 2.8 |
13. Max ACH | 4.1 |
14. Avg ACH | 3.7 |
15. eACH | 0 |
16. Filter MERV | --- |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 923.4 |
22. cuft | 9234 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 114. Diffuser air volume (cfm) 500. % Outside air 100. Calculated air volume (cfm) outside 500. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 500. ACH outside 2.8. ACH merv filter return air 0.0. ACH total 2.8. ACH Copy paste check (uses total or outside) 2.8. Room 204. Diffuser air volume (cfm) 680. % Outside air 100. Calculated air volume (cfm) outside 680. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 680. ACH outside 3.8. ACH merv filter return air 0.0. ACH total 3.8. ACH Copy paste check (uses total or outside) 3.8. Room 210. Diffuser air volume (cfm) 650. % Outside air 100. Calculated air volume (cfm) outside 650. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 650. ACH outside 3.7. ACH merv filter return air 0.0. ACH total 3.7. ACH Copy paste check (uses total or outside) 3.7. Room 302. Diffuser air volume (cfm) 710. % Outside air 100. Calculated air volume (cfm) outside 710. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 710. ACH outside 4.0. ACH merv filter return air 0.0. ACH total 4.0. ACH Copy paste check (uses total or outside) 4. Room 314. Diffuser air volume (cfm) 730. % Outside air 100. Calculated air volume (cfm) outside 730. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 730. ACH outside 4.1. ACH merv filter return air 0.0. ACH total 4.1. ACH Copy paste check (uses total or outside) 4.1. Room 137. Diffuser air volume (cfm) 295. % Outside air 100. Calculated air volume (cfm) outside 295. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 295. ACH outside 1.9. ACH merv filter return air 0.0. ACH total 1.9. ACH Copy paste check (uses total or outside) 1.9. |