About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameEast Boston High School
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited HVAC
12. Min ACH0.8
13. Max ACH4
14. Avg ACH2.3
15. eACH0
16. Filter MERV90
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft913.5
22. cuft9135
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 159. Diffuser air volume (cfm) 466. % Outside air 100. Calculated air volume (cfm) outside 466. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 466. ACH outside 2.9. ACH merv filter return air 0.0. ACH total 2.9. ACH Copy paste check (uses total or outside) 2.

Room 241. Diffuser air volume (cfm) 590. % Outside air 100. Calculated air volume (cfm) outside 590. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 590. ACH outside 4.0. ACH merv filter return air 0.0. ACH total 4.0. ACH Copy paste check (uses total or outside) 4.7.

Room 259. Diffuser air volume (cfm) 122. % Outside air 100. Calculated air volume (cfm) outside 122. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 122. ACH outside 0.8. ACH merv filter return air 0.0. ACH total 0.8. ACH Copy paste check (uses total or outside) 0.6.

Room 355. Diffuser air volume (cfm) 460. % Outside air 100. Calculated air volume (cfm) outside 460. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 460. ACH outside 2.8. ACH merv filter return air 0.0. ACH total 2.8. ACH Copy paste check (uses total or outside) 2.8.

Room 41. Diffuser air volume (cfm) 345. % Outside air 100. Calculated air volume (cfm) outside 345. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 345. ACH outside 1.8. ACH merv filter return air 0.0. ACH total 1.8. ACH Copy paste check (uses total or outside) 1.8.

Room 105. Diffuser air volume (cfm) 1365. % Outside air 50. Calculated air volume (cfm) outside 683. Calculated air volume (cfm) return 682. Filter merv rating 90. Filter efficiency (decimal) 0.9. Combined air volume (cfm) 1297. ACH outside 4.5. ACH merv filter return air 4.5. ACH total 8.5. ACH Copy paste check (uses total or outside) 8.5.