0. Space TypeBOS-School
1. Establishment NameEverett Edward Elementary
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited HVAC
12. Min ACH0.9
13. Max ACH2.9
14. Avg ACH1.9
15. eACH0
16. Filter MERV13
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft752.4
22. cuft7524
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 14. Diffuser air volume (cfm) 390. % Outside air 100. Calculated air volume (cfm) outside 390. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 390. ACH outside 2.9. ACH merv filter return air 0.0. ACH total 2.9. ACH Copy paste check (uses total or outside) 2.9.

Room 2. Diffuser air volume (cfm) 226. % Outside air 100. Calculated air volume (cfm) outside 226. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 226. ACH outside 1.7. ACH merv filter return air 0.0. ACH total 1.7. ACH Copy paste check (uses total or outside) 1.7.

Room 4. Diffuser air volume (cfm) 200. % Outside air 100. Calculated air volume (cfm) outside 200. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 200. ACH outside 1.5. ACH merv filter return air 0.0. ACH total 1.5. ACH Copy paste check (uses total or outside) 1.5.

Room 6. Diffuser air volume (cfm) 130. % Outside air 100. Calculated air volume (cfm) outside 130. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 130. ACH outside 0.9. ACH merv filter return air 0.0. ACH total 0.9. ACH Copy paste check (uses total or outside) 0.9.

Room 7. Diffuser air volume (cfm) 240. % Outside air 100. Calculated air volume (cfm) outside 240. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 240. ACH outside 2.3. ACH merv filter return air 0.0. ACH total 2.3. ACH Copy paste check (uses total or outside) 2.3.

Room 128*. Diffuser air volume (cfm) 114. % Outside air 70. Calculated air volume (cfm) outside 80. Calculated air volume (cfm) return 34. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 109. ACH outside 0.6. ACH merv filter return air 0.3. ACH total 0.9. ACH Copy paste check (uses total or outside) 0.8.