0. Space Type | BOS-School |
1. Establishment Name | Haley Dennis Pilot School K 8 |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited HVAC |
12. Min ACH | 0.9 |
13. Max ACH | 6.4 |
14. Avg ACH | 3.1 |
15. eACH | 0 |
16. Filter MERV | --- |
17. Percent Outside Air | 69.7 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 4 |
21. sqft | 800.4 |
22. cuft | 8004 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 129. Diffuser air volume (cfm) 536. % Outside air 70. Calculated air volume (cfm) outside 375. Calculated air volume (cfm) return 161. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 512. ACH outside 2.9. ACH merv filter return air 1.2. ACH total 3.9. ACH Copy paste check (uses total or outside) 3.3. Room 130. Diffuser air volume (cfm) 311. % Outside air 70. Calculated air volume (cfm) outside 218. Calculated air volume (cfm) return 93. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 297. ACH outside 1.0. ACH merv filter return air 0.4. ACH total 1.3. ACH Copy paste check (uses total or outside) 1.4. Room 158. Diffuser air volume (cfm) 625. % Outside air 70. Calculated air volume (cfm) outside 437. Calculated air volume (cfm) return 187. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 596. ACH outside 4.7. ACH merv filter return air 2.0. ACH total 6.4. ACH Copy paste check (uses total or outside) 6.4. Room 101. Diffuser air volume (cfm) 247. % Outside air 100. Calculated air volume (cfm) outside 247. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 247. ACH outside 1.9. ACH merv filter return air 0.0. ACH total 1.9. ACH Copy paste check (uses total or outside) 1.9. |