0. Space TypeBOS-School
1. Establishment NameHaley Dennis Pilot School K 8
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited HVAC
12. Min ACH0.9
13. Max ACH6.4
14. Avg ACH3.1
15. eACH0
16. Filter MERV---
17. Percent Outside Air69.7
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms4
21. sqft800.4
22. cuft8004
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 129. Diffuser air volume (cfm) 536. % Outside air 70. Calculated air volume (cfm) outside 375. Calculated air volume (cfm) return 161. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 512. ACH outside 2.9. ACH merv filter return air 1.2. ACH total 3.9. ACH Copy paste check (uses total or outside) 3.3.

Room 130. Diffuser air volume (cfm) 311. % Outside air 70. Calculated air volume (cfm) outside 218. Calculated air volume (cfm) return 93. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 297. ACH outside 1.0. ACH merv filter return air 0.4. ACH total 1.3. ACH Copy paste check (uses total or outside) 1.4.

Room 158. Diffuser air volume (cfm) 625. % Outside air 70. Calculated air volume (cfm) outside 437. Calculated air volume (cfm) return 187. Filter merv rating 13. Filter efficiency (decimal) 0.85. Combined air volume (cfm) 596. ACH outside 4.7. ACH merv filter return air 2.0. ACH total 6.4. ACH Copy paste check (uses total or outside) 6.4.

Room 101. Diffuser air volume (cfm) 247. % Outside air 100. Calculated air volume (cfm) outside 247. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 247. ACH outside 1.9. ACH merv filter return air 0.0. ACH total 1.9. ACH Copy paste check (uses total or outside) 1.9.