0. Space Type | BOS-School |
1. Establishment Name | Mary Lyon K 8 Lower |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited HVAC |
12. Min ACH | 2.6 |
13. Max ACH | 7 |
14. Avg ACH | 5.1 |
15. eACH | 0 |
16. Filter MERV | --- |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 1123.2 |
22. cuft | 11232 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 109. Diffuser air volume (cfm) 355. % Outside air 100. Calculated air volume (cfm) outside 355. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 355. ACH outside 6.7. ACH merv filter return air 0.0. ACH total 6.7. ACH Copy paste check (uses total or outside) 6.7. Room 203. Diffuser air volume (cfm) 545. % Outside air 100. Calculated air volume (cfm) outside 545. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 545. ACH outside 5.8. ACH merv filter return air 0.0. ACH total 5.8. ACH Copy paste check (uses total or outside) 5.8. Room 205. Diffuser air volume (cfm) 330. % Outside air 100. Calculated air volume (cfm) outside 330. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 330. ACH outside 3.5. ACH merv filter return air 0.0. ACH total 3.5. ACH Copy paste check (uses total or outside) 3.5. Room 207. Diffuser air volume (cfm) 650. % Outside air 100. Calculated air volume (cfm) outside 650. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 650. ACH outside 7.0. ACH merv filter return air 0.0. ACH total 7.0. ACH Copy paste check (uses total or outside) 7. Room 208. Diffuser air volume (cfm) 510. % Outside air 100. Calculated air volume (cfm) outside 510. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 510. ACH outside 5.5. ACH merv filter return air 0.0. ACH total 5.5. ACH Copy paste check (uses total or outside) 5.5. Room 206. Diffuser air volume (cfm) 442. % Outside air 100. Calculated air volume (cfm) outside 442. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 442. ACH outside 2.4. ACH merv filter return air 0.0. ACH total 2.4. ACH Copy paste check (uses total or outside) 2.4. |