0. Space TypeBOS-School
1. Establishment NameMary Lyon K 8 Lower
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited HVAC
12. Min ACH2.6
13. Max ACH7
14. Avg ACH5.1
15. eACH0
16. Filter MERV---
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1123.2
22. cuft11232
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 109. Diffuser air volume (cfm) 355. % Outside air 100. Calculated air volume (cfm) outside 355. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 355. ACH outside 6.7. ACH merv filter return air 0.0. ACH total 6.7. ACH Copy paste check (uses total or outside) 6.7.

Room 203. Diffuser air volume (cfm) 545. % Outside air 100. Calculated air volume (cfm) outside 545. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 545. ACH outside 5.8. ACH merv filter return air 0.0. ACH total 5.8. ACH Copy paste check (uses total or outside) 5.8.

Room 205. Diffuser air volume (cfm) 330. % Outside air 100. Calculated air volume (cfm) outside 330. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 330. ACH outside 3.5. ACH merv filter return air 0.0. ACH total 3.5. ACH Copy paste check (uses total or outside) 3.5.

Room 207. Diffuser air volume (cfm) 650. % Outside air 100. Calculated air volume (cfm) outside 650. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 650. ACH outside 7.0. ACH merv filter return air 0.0. ACH total 7.0. ACH Copy paste check (uses total or outside) 7.

Room 208. Diffuser air volume (cfm) 510. % Outside air 100. Calculated air volume (cfm) outside 510. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 510. ACH outside 5.5. ACH merv filter return air 0.0. ACH total 5.5. ACH Copy paste check (uses total or outside) 5.5.

Room 206. Diffuser air volume (cfm) 442. % Outside air 100. Calculated air volume (cfm) outside 442. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 442. ACH outside 2.4. ACH merv filter return air 0.0. ACH total 2.4. ACH Copy paste check (uses total or outside) 2.4.