0. Space TypeBOS-School
1. Establishment NameMather Elementary
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited HVAC
12. Min ACH0.5
13. Max ACH3.8
14. Avg ACH2
15. eACH0
16. Filter MERV---
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft942.5
22. cuft9425
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 214. Diffuser air volume (cfm) 203. % Outside air 100. Calculated air volume (cfm) outside 203. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 203. ACH outside 1.1. ACH merv filter return air 0.0. ACH total 1.1. ACH Copy paste check (uses total or outside) 1.1.

Room 302. Diffuser air volume (cfm) 690. % Outside air 100. Calculated air volume (cfm) outside 690. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 690. ACH outside 3.8. ACH merv filter return air 0.0. ACH total 3.8. ACH Copy paste check (uses total or outside) 3.8.

Room 318. Diffuser air volume (cfm) 90. % Outside air 100. Calculated air volume (cfm) outside 90. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 90. ACH outside 0.5. ACH merv filter return air 0.0. ACH total 0.5. ACH Copy paste check (uses total or outside) 0.5.

Room 402. Diffuser air volume (cfm) 422. % Outside air 100. Calculated air volume (cfm) outside 422. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 422. ACH outside 2.3. ACH merv filter return air 0.0. ACH total 2.3. ACH Copy paste check (uses total or outside) 2.3.

Room 414. Diffuser air volume (cfm) 395. % Outside air 100. Calculated air volume (cfm) outside 395. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 395. ACH outside 2.2. ACH merv filter return air 0.0. ACH total 2.2. ACH Copy paste check (uses total or outside) 2.2.

Room 12. Diffuser air volume (cfm) 340. % Outside air 100. Calculated air volume (cfm) outside 340. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 340. ACH outside 2.2. ACH merv filter return air 0.0. ACH total 2.2. ACH Copy paste check (uses total or outside) 2.1.