0. Space Type | BOS-School |
1. Establishment Name | Nathan Hale Elementary |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited HVAC |
12. Min ACH | 1.1 |
13. Max ACH | 3.8 |
14. Avg ACH | 2.4 |
15. eACH | 0 |
16. Filter MERV | --- |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 931.5 |
22. cuft | 9315 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 107. Diffuser air volume (cfm) 205. % Outside air 100. Calculated air volume (cfm) outside 205. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 205. ACH outside 1.1. ACH merv filter return air 0.0. ACH total 1.1. ACH Copy paste check (uses total or outside) 1.1. Room 108. Diffuser air volume (cfm) 235. % Outside air 100. Calculated air volume (cfm) outside 235. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 235. ACH outside 1.5. ACH merv filter return air 0.0. ACH total 1.5. ACH Copy paste check (uses total or outside) 1.5. Room 201. Diffuser air volume (cfm) 395. % Outside air 100. Calculated air volume (cfm) outside 395. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 395. ACH outside 1.8. ACH merv filter return air 0.0. ACH total 1.8. ACH Copy paste check (uses total or outside) 1.8. Room 202. Diffuser air volume (cfm) 395. % Outside air 100. Calculated air volume (cfm) outside 395. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 395. ACH outside 2.8. ACH merv filter return air 0.0. ACH total 2.8. ACH Copy paste check (uses total or outside) 2.7. Room 206. Diffuser air volume (cfm) 600. % Outside air 100. Calculated air volume (cfm) outside 600. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 600. ACH outside 3.8. ACH merv filter return air 0.0. ACH total 3.8. ACH Copy paste check (uses total or outside) 3.8. Room 136. Diffuser air volume (cfm) 130. % Outside air 100. Calculated air volume (cfm) outside 130. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 130. ACH outside 0.8. ACH merv filter return air 0.0. ACH total 0.8. ACH Copy paste check (uses total or outside) 0.9. |