About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameNathan Hale Elementary
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited HVAC
12. Min ACH1.1
13. Max ACH3.8
14. Avg ACH2.4
15. eACH0
16. Filter MERV---
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft931.5
22. cuft9315
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 107. Diffuser air volume (cfm) 205. % Outside air 100. Calculated air volume (cfm) outside 205. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 205. ACH outside 1.1. ACH merv filter return air 0.0. ACH total 1.1. ACH Copy paste check (uses total or outside) 1.1.

Room 108. Diffuser air volume (cfm) 235. % Outside air 100. Calculated air volume (cfm) outside 235. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 235. ACH outside 1.5. ACH merv filter return air 0.0. ACH total 1.5. ACH Copy paste check (uses total or outside) 1.5.

Room 201. Diffuser air volume (cfm) 395. % Outside air 100. Calculated air volume (cfm) outside 395. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 395. ACH outside 1.8. ACH merv filter return air 0.0. ACH total 1.8. ACH Copy paste check (uses total or outside) 1.8.

Room 202. Diffuser air volume (cfm) 395. % Outside air 100. Calculated air volume (cfm) outside 395. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 395. ACH outside 2.8. ACH merv filter return air 0.0. ACH total 2.8. ACH Copy paste check (uses total or outside) 2.7.

Room 206. Diffuser air volume (cfm) 600. % Outside air 100. Calculated air volume (cfm) outside 600. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 600. ACH outside 3.8. ACH merv filter return air 0.0. ACH total 3.8. ACH Copy paste check (uses total or outside) 3.8.

Room 136. Diffuser air volume (cfm) 130. % Outside air 100. Calculated air volume (cfm) outside 130. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 130. ACH outside 0.8. ACH merv filter return air 0.0. ACH total 0.8. ACH Copy paste check (uses total or outside) 0.9.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Nathan Hale Elementary.txt. Feel free to add Survey data. Nathan Hale Elementary

CAB v 0.11 R -1

08:27:19 Start Time
08:27:19 End Time
0 Seconds

5.026003 cab pid: 3836151 httpd pid: error pid: