![]() |
About Us | Contact Us |
0. Space Type | BOS-School |
1. Establishment Name | New Mission High School |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited HVAC |
12. Min ACH | 0.7 |
13. Max ACH | 2.2 |
14. Avg ACH | 1.2 |
15. eACH | 0 |
16. Filter MERV | --- |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 902.4 |
22. cuft | 9024 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 147. Diffuser air volume (cfm) 143. % Outside air 100. Calculated air volume (cfm) outside 143. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 143. ACH outside 1.0. ACH merv filter return air 0.0. ACH total 1.0. ACH Copy paste check (uses total or outside) 1. Room 233. Diffuser air volume (cfm) 381. % Outside air 100. Calculated air volume (cfm) outside 381. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 381. ACH outside 2.2. ACH merv filter return air 0.0. ACH total 2.2. ACH Copy paste check (uses total or outside) 2.2. Room 248. Diffuser air volume (cfm) 135. % Outside air 100. Calculated air volume (cfm) outside 135. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 135. ACH outside 0.9. ACH merv filter return air 0.0. ACH total 0.9. ACH Copy paste check (uses total or outside) 0.9. Room 40. Diffuser air volume (cfm) 181. % Outside air 100. Calculated air volume (cfm) outside 181. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 181. ACH outside 1.8. ACH merv filter return air 0.0. ACH total 1.8. ACH Copy paste check (uses total or outside) 1.8. Room 46. Diffuser air volume (cfm) 115. % Outside air 100. Calculated air volume (cfm) outside 115. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 115. ACH outside 0.7. ACH merv filter return air 0.0. ACH total 0.7. ACH Copy paste check (uses total or outside) 0.7. Room 107. Diffuser air volume (cfm) 91. % Outside air 100. Calculated air volume (cfm) outside 91. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 91. ACH outside 0.6. ACH merv filter return air 0.0. ACH total 0.6. ACH Copy paste check (uses total or outside) 0.6. |