About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameNew Mission High School
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited HVAC
12. Min ACH0.7
13. Max ACH2.2
14. Avg ACH1.2
15. eACH0
16. Filter MERV---
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft902.4
22. cuft9024
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 147. Diffuser air volume (cfm) 143. % Outside air 100. Calculated air volume (cfm) outside 143. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 143. ACH outside 1.0. ACH merv filter return air 0.0. ACH total 1.0. ACH Copy paste check (uses total or outside) 1.

Room 233. Diffuser air volume (cfm) 381. % Outside air 100. Calculated air volume (cfm) outside 381. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 381. ACH outside 2.2. ACH merv filter return air 0.0. ACH total 2.2. ACH Copy paste check (uses total or outside) 2.2.

Room 248. Diffuser air volume (cfm) 135. % Outside air 100. Calculated air volume (cfm) outside 135. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 135. ACH outside 0.9. ACH merv filter return air 0.0. ACH total 0.9. ACH Copy paste check (uses total or outside) 0.9.

Room 40. Diffuser air volume (cfm) 181. % Outside air 100. Calculated air volume (cfm) outside 181. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 181. ACH outside 1.8. ACH merv filter return air 0.0. ACH total 1.8. ACH Copy paste check (uses total or outside) 1.8.

Room 46. Diffuser air volume (cfm) 115. % Outside air 100. Calculated air volume (cfm) outside 115. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 115. ACH outside 0.7. ACH merv filter return air 0.0. ACH total 0.7. ACH Copy paste check (uses total or outside) 0.7.

Room 107. Diffuser air volume (cfm) 91. % Outside air 100. Calculated air volume (cfm) outside 91. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 91. ACH outside 0.6. ACH merv filter return air 0.0. ACH total 0.6. ACH Copy paste check (uses total or outside) 0.6.