0. Space Type | BOS-School |
1. Establishment Name | Quincy Josiah Upper School |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited HVAC |
12. Min ACH | 0.2 |
13. Max ACH | 0.9 |
14. Avg ACH | 0.5 |
15. eACH | 0 |
16. Filter MERV | --- |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 882 |
22. cuft | 8820 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 108/109. Diffuser air volume (cfm) 285. % Outside air 100. Calculated air volume (cfm) outside 285. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 285. ACH outside 0.7. ACH merv filter return air 0.0. ACH total 0.7. ACH Copy paste check (uses total or outside) 0.7. Room 208. Diffuser air volume (cfm) 115. % Outside air 100. Calculated air volume (cfm) outside 115. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 115. ACH outside 0.9. ACH merv filter return air 0.0. ACH total 0.9. ACH Copy paste check (uses total or outside) 0.9. Room 217. Diffuser air volume (cfm) 83. % Outside air 100. Calculated air volume (cfm) outside 83. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 83. ACH outside 0.6. ACH merv filter return air 0.0. ACH total 0.6. ACH Copy paste check (uses total or outside) 0.6. Room 307. Diffuser air volume (cfm) 30. % Outside air 100. Calculated air volume (cfm) outside 30. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 30. ACH outside 0.2. ACH merv filter return air 0.0. ACH total 0.2. ACH Copy paste check (uses total or outside) 0.2. Room 317. Diffuser air volume (cfm) 35. % Outside air 100. Calculated air volume (cfm) outside 35. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 35. ACH outside 0.3. ACH merv filter return air 0.0. ACH total 0.3. ACH Copy paste check (uses total or outside) 0.3. Room 1. Diffuser air volume (cfm) 233. % Outside air 100. Calculated air volume (cfm) outside 233. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 233. ACH outside 1.6. ACH merv filter return air 0.0. ACH total 1.6. ACH Copy paste check (uses total or outside) 1.6. |