0. Space Type | BOS-School |
1. Establishment Name | Roosevelt Franklin D K 8 K1 1 |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited HVAC |
12. Min ACH | 1.6 |
13. Max ACH | 3.5 |
14. Avg ACH | 2.5 |
15. eACH | 0 |
16. Filter MERV | --- |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 1159.6 |
22. cuft | 11596 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 2. Diffuser air volume (cfm) 247. % Outside air 100. Calculated air volume (cfm) outside 247. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 247. ACH outside 1.7. ACH merv filter return air 0.0. ACH total 1.7. ACH Copy paste check (uses total or outside) 1.7. Room 3. Diffuser air volume (cfm) 261. % Outside air 100. Calculated air volume (cfm) outside 261. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 261. ACH outside 1.8. ACH merv filter return air 0.0. ACH total 1.8. ACH Copy paste check (uses total or outside) 1.8. Room 4. Diffuser air volume (cfm) 500. % Outside air 100. Calculated air volume (cfm) outside 500. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 500. ACH outside 3.4. ACH merv filter return air 0.0. ACH total 3.4. ACH Copy paste check (uses total or outside) 3.4. Room 5. Diffuser air volume (cfm) 504. % Outside air 100. Calculated air volume (cfm) outside 504. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 504. ACH outside 3.4. ACH merv filter return air 0.0. ACH total 3.4. ACH Copy paste check (uses total or outside) 3.4. Room 6. Diffuser air volume (cfm) 518. % Outside air 100. Calculated air volume (cfm) outside 518. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 518. ACH outside 3.5. ACH merv filter return air 0.0. ACH total 3.5. ACH Copy paste check (uses total or outside) 3.5. Room 102. Diffuser air volume (cfm) 200. % Outside air 100. Calculated air volume (cfm) outside 200. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 200. ACH outside 1.0. ACH merv filter return air 0.0. ACH total 1.0. ACH Copy paste check (uses total or outside) 1. |