About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameRoosevelt Franklin D K 8 K1 1
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited HVAC
12. Min ACH1.6
13. Max ACH3.5
14. Avg ACH2.5
15. eACH0
16. Filter MERV---
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1159.6
22. cuft11596
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 2. Diffuser air volume (cfm) 247. % Outside air 100. Calculated air volume (cfm) outside 247. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 247. ACH outside 1.7. ACH merv filter return air 0.0. ACH total 1.7. ACH Copy paste check (uses total or outside) 1.7.

Room 3. Diffuser air volume (cfm) 261. % Outside air 100. Calculated air volume (cfm) outside 261. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 261. ACH outside 1.8. ACH merv filter return air 0.0. ACH total 1.8. ACH Copy paste check (uses total or outside) 1.8.

Room 4. Diffuser air volume (cfm) 500. % Outside air 100. Calculated air volume (cfm) outside 500. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 500. ACH outside 3.4. ACH merv filter return air 0.0. ACH total 3.4. ACH Copy paste check (uses total or outside) 3.4.

Room 5. Diffuser air volume (cfm) 504. % Outside air 100. Calculated air volume (cfm) outside 504. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 504. ACH outside 3.4. ACH merv filter return air 0.0. ACH total 3.4. ACH Copy paste check (uses total or outside) 3.4.

Room 6. Diffuser air volume (cfm) 518. % Outside air 100. Calculated air volume (cfm) outside 518. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 518. ACH outside 3.5. ACH merv filter return air 0.0. ACH total 3.5. ACH Copy paste check (uses total or outside) 3.5.

Room 102. Diffuser air volume (cfm) 200. % Outside air 100. Calculated air volume (cfm) outside 200. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 200. ACH outside 1.0. ACH merv filter return air 0.0. ACH total 1.0. ACH Copy paste check (uses total or outside) 1.