0. Space Type | BOS-School |
1. Establishment Name | Russell William E Elementary |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited HVAC |
12. Min ACH | 0 |
13. Max ACH | 1.6 |
14. Avg ACH | 0.7 |
15. eACH | 0 |
16. Filter MERV | --- |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 1248 |
22. cuft | 12480 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 109. Diffuser air volume (cfm) 134. % Outside air 100. Calculated air volume (cfm) outside 134. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 134. ACH outside 0.7. ACH merv filter return air 0.0. ACH total 0.7. ACH Copy paste check (uses total or outside) 0.7. Room 211*. Diffuser air volume (cfm) 0. % Outside air 100. Calculated air volume (cfm) outside 0. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 0. ACH outside 0.0. ACH merv filter return air 0.0. ACH total 0.0. ACH Copy paste check (uses total or outside) 0. Room 214A*. Diffuser air volume (cfm) 0. % Outside air 100. Calculated air volume (cfm) outside 0. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 0. ACH outside 0.0. ACH merv filter return air 0.0. ACH total 0.0. ACH Copy paste check (uses total or outside) 0. Room 215. Diffuser air volume (cfm) 295. % Outside air 100. Calculated air volume (cfm) outside 295. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 295. ACH outside 1.6. ACH merv filter return air 0.0. ACH total 1.6. ACH Copy paste check (uses total or outside) 1.6. Room 217. Diffuser air volume (cfm) 180. % Outside air 100. Calculated air volume (cfm) outside 180. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 180. ACH outside 1.0. ACH merv filter return air 0.0. ACH total 1.0. ACH Copy paste check (uses total or outside) 1. Room 104. Diffuser air volume (cfm) 500. % Outside air 100. Calculated air volume (cfm) outside 500. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 500. ACH outside 2.4. ACH merv filter return air 0.0. ACH total 2.4. ACH Copy paste check (uses total or outside) 2.4. |