Building Data Report

0. Space TypeBOS-School
1. Establishment NameRussell William E Elementary
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited HVAC
12. Min ACH0
13. Max ACH1.6
14. Avg ACH0.7
15. eACH0
16. Filter MERV---
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft1248
22. cuft12480
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 109. Diffuser air volume (cfm) 134. % Outside air 100. Calculated air volume (cfm) outside 134. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 134. ACH outside 0.7. ACH merv filter return air 0.0. ACH total 0.7. ACH Copy paste check (uses total or outside) 0.7.

Room 211*. Diffuser air volume (cfm) 0. % Outside air 100. Calculated air volume (cfm) outside 0. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 0. ACH outside 0.0. ACH merv filter return air 0.0. ACH total 0.0. ACH Copy paste check (uses total or outside) 0.

Room 214A*. Diffuser air volume (cfm) 0. % Outside air 100. Calculated air volume (cfm) outside 0. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 0. ACH outside 0.0. ACH merv filter return air 0.0. ACH total 0.0. ACH Copy paste check (uses total or outside) 0.

Room 215. Diffuser air volume (cfm) 295. % Outside air 100. Calculated air volume (cfm) outside 295. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 295. ACH outside 1.6. ACH merv filter return air 0.0. ACH total 1.6. ACH Copy paste check (uses total or outside) 1.6.

Room 217. Diffuser air volume (cfm) 180. % Outside air 100. Calculated air volume (cfm) outside 180. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 180. ACH outside 1.0. ACH merv filter return air 0.0. ACH total 1.0. ACH Copy paste check (uses total or outside) 1.

Room 104. Diffuser air volume (cfm) 500. % Outside air 100. Calculated air volume (cfm) outside 500. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 500. ACH outside 2.4. ACH merv filter return air 0.0. ACH total 2.4. ACH Copy paste check (uses total or outside) 2.4.