About Us | Contact Us |
0. Space Type | BOS-School |
1. Establishment Name | Winship F Lyman Elementary |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | |
12. Min ACH | 2.4 |
13. Max ACH | 2.9 |
14. Avg ACH | 2.5 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 100 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 0 |
22. cuft | CLASSROOM VOLUME (FT3) |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 106. Diffuser air volume (cfm) 595. % Outside air 100. Calculated air volume (cfm) outside 595. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 595. ACH outside 2.9. ACH merv filter return air 0.0. ACH total 2.9. ACH Copy paste check (uses total or outside) 2.9. Room 207. Diffuser air volume (cfm) 520. % Outside air 100. Calculated air volume (cfm) outside 520. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 520. ACH outside 2.5. ACH merv filter return air 0.0. ACH total 2.5. ACH Copy paste check (uses total or outside) 2.5. Room 209. Diffuser air volume (cfm) 490. % Outside air 100. Calculated air volume (cfm) outside 490. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 490. ACH outside 2.4. ACH merv filter return air 0.0. ACH total 2.4. ACH Copy paste check (uses total or outside) 2.4. Room 210. Diffuser air volume (cfm) 580. % Outside air 100. Calculated air volume (cfm) outside 580. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 580. ACH outside 2.8. ACH merv filter return air 0.0. ACH total 2.8. ACH Copy paste check (uses total or outside) 2.8. Room 212. Diffuser air volume (cfm) 495. % Outside air 100. Calculated air volume (cfm) outside 495. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 495. ACH outside 2.4. ACH merv filter return air 0.0. ACH total 2.4. ACH Copy paste check (uses total or outside) 2.4. Room ROOM. % Outside air % OUTSIDE AIR . Calculated air volume (cfm) outside OUTSIDE AIR (CFM). Calculated air volume (cfm) return RETURN AIR (CFM). Combined air volume (cfm) TOTAL AIR (CFM). ACH outside AIR CHANGES PER HOUR OUTSIDE. ACH merv filter return air AIR CHANGES PER HOUR MERV FILTER RETURN AIR. ACH total AIR CHANGES PER HOUR TOTAL. ACH Copy paste check (uses total or outside) copy paste check (uses outside). |