About Us Contact Us

Building Data Report

0. Space TypeBOS-School
1. Establishment NameWinship F Lyman Elementary
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. Technology
12. Min ACH2.4
13. Max ACH2.9
14. Avg ACH2.5
15. eACH0
16. Filter MERV
17. Percent Outside Air100
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft0
22. cuftCLASSROOM VOLUME (FT3)
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 106. Diffuser air volume (cfm) 595. % Outside air 100. Calculated air volume (cfm) outside 595. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 595. ACH outside 2.9. ACH merv filter return air 0.0. ACH total 2.9. ACH Copy paste check (uses total or outside) 2.9.

Room 207. Diffuser air volume (cfm) 520. % Outside air 100. Calculated air volume (cfm) outside 520. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 520. ACH outside 2.5. ACH merv filter return air 0.0. ACH total 2.5. ACH Copy paste check (uses total or outside) 2.5.

Room 209. Diffuser air volume (cfm) 490. % Outside air 100. Calculated air volume (cfm) outside 490. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 490. ACH outside 2.4. ACH merv filter return air 0.0. ACH total 2.4. ACH Copy paste check (uses total or outside) 2.4.

Room 210. Diffuser air volume (cfm) 580. % Outside air 100. Calculated air volume (cfm) outside 580. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 580. ACH outside 2.8. ACH merv filter return air 0.0. ACH total 2.8. ACH Copy paste check (uses total or outside) 2.8.

Room 212. Diffuser air volume (cfm) 495. % Outside air 100. Calculated air volume (cfm) outside 495. Calculated air volume (cfm) return 0. Filter efficiency (decimal) 0. Combined air volume (cfm) 495. ACH outside 2.4. ACH merv filter return air 0.0. ACH total 2.4. ACH Copy paste check (uses total or outside) 2.4.

Room ROOM. % Outside air % OUTSIDE AIR . Calculated air volume (cfm) outside OUTSIDE AIR (CFM). Calculated air volume (cfm) return RETURN AIR (CFM). Combined air volume (cfm) TOTAL AIR (CFM). ACH outside AIR CHANGES PER HOUR OUTSIDE. ACH merv filter return air AIR CHANGES PER HOUR MERV FILTER RETURN AIR. ACH total AIR CHANGES PER HOUR TOTAL. ACH Copy paste check (uses total or outside) copy paste check (uses outside).