Building Data Report

0. Space TypeBOS-School
1. Establishment NameAnother Course to College
2. Addressaddress
3. CityBoston
4. State / ProvinceMA
5. CountryUSA
6. Date03/21/2021
7. Data SourceSchool District
8. Performed byExternal Company
9. Company Name Address ContactCashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880
10. Requirement SourceBoston School 3 ACH guideline
11. TechnologyNatural Ventilation Windows and Limited Univent HVAC
12. Min ACH1.6
13. Max ACH3.6
14. Avg ACH2.6
15. eACH0
16. Filter MERV
17. Percent Outside Air69.1
18. ON and Ventilates Entire Indoor AreaYes
19. Vent Clearance min 6 ftYes
20. No of Rooms6
21. sqft800.4
22. cuft8004
23. No of Buildings1
24. Comments Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH.

Room 135. % Outside air 80. Calculated air volume (cfm) outside 264. Calculated air volume (cfm) return 65. Combined air volume (cfm) 329. ACH outside 1.8. ACH merv filter return air 0.4. ACH total 2.3. ACH Copy paste check (uses total or outside) 1.8.

Room 141. % Outside air 48. Calculated air volume (cfm) outside 152. Calculated air volume (cfm) return 165. Combined air volume (cfm) 317. ACH outside 1.1. ACH merv filter return air 1.2. ACH total 2.3. ACH Copy paste check (uses total or outside) 1.1.

Room 216. % Outside air 71. Calculated air volume (cfm) outside 157. Calculated air volume (cfm) return 65. Combined air volume (cfm) 222. ACH outside 1.1. ACH merv filter return air 0.5. ACH total 1.6. ACH Copy paste check (uses total or outside) 1.1.

Room 211. % Outside air 75. Calculated air volume (cfm) outside 356. Calculated air volume (cfm) return 120. Combined air volume (cfm) 476. ACH outside 2.6. ACH merv filter return air 0.9. ACH total 3.5. ACH Copy paste check (uses total or outside) 2.6.

Room 213. % Outside air 83. Calculated air volume (cfm) outside 317. Calculated air volume (cfm) return 67. Combined air volume (cfm) 384. ACH outside 2.3. ACH merv filter return air 0.5. ACH total 2.8. ACH Copy paste check (uses total or outside) 2.3.

Room 103. % Outside air 50. Calculated air volume (cfm) outside 222. Calculated air volume (cfm) return 220. Combined air volume (cfm) 442. ACH outside 1.7. ACH merv filter return air 1.6. ACH total 3.3. ACH Copy paste check (uses total or outside) 1.7.


Facility Panel

Note: There is no Existing Survey or Realtime Data file: surveys/Another Course to College.txt. Feel free to add Survey data. Another Course to College