0. Space Type | BOS-School |
1. Establishment Name | Another Course to College |
2. Address | address |
3. City | Boston |
4. State / Province | MA |
5. Country | USA |
6. Date | 03/21/2021 |
7. Data Source | School District |
8. Performed by | External Company |
9. Company Name Address Contact | Cashins & Associates, Inc. 599 North Ave #8, Wakefield, MA 01880 |
10. Requirement Source | Boston School 3 ACH guideline |
11. Technology | Natural Ventilation Windows and Limited Univent HVAC |
12. Min ACH | 1.6 |
13. Max ACH | 3.6 |
14. Avg ACH | 2.6 |
15. eACH | 0 |
16. Filter MERV | |
17. Percent Outside Air | 69.1 |
18. ON and Ventilates Entire Indoor Area | Yes |
19. Vent Clearance min 6 ft | Yes |
20. No of Rooms | 6 |
21. sqft | 800.4 |
22. cuft | 8004 |
23. No of Buildings | 1 |
24. Comments | Source Boston School District March 18, 2021. https://www.bostonpublicschools.org/Page/8463 . https://drive.google.com/file/d/1bzam7XeMQDjjv7Og_86PS41K78hBEOfT/view . assumed 10ft ceiling. wACH windows provided in dataset. Calculated wACH from measured CFM rates in dataset do not match. Differences due to errors. Did not use calculated wACH. Room 135. % Outside air 80. Calculated air volume (cfm) outside 264. Calculated air volume (cfm) return 65. Combined air volume (cfm) 329. ACH outside 1.8. ACH merv filter return air 0.4. ACH total 2.3. ACH Copy paste check (uses total or outside) 1.8. Room 141. % Outside air 48. Calculated air volume (cfm) outside 152. Calculated air volume (cfm) return 165. Combined air volume (cfm) 317. ACH outside 1.1. ACH merv filter return air 1.2. ACH total 2.3. ACH Copy paste check (uses total or outside) 1.1. Room 216. % Outside air 71. Calculated air volume (cfm) outside 157. Calculated air volume (cfm) return 65. Combined air volume (cfm) 222. ACH outside 1.1. ACH merv filter return air 0.5. ACH total 1.6. ACH Copy paste check (uses total or outside) 1.1. Room 211. % Outside air 75. Calculated air volume (cfm) outside 356. Calculated air volume (cfm) return 120. Combined air volume (cfm) 476. ACH outside 2.6. ACH merv filter return air 0.9. ACH total 3.5. ACH Copy paste check (uses total or outside) 2.6. Room 213. % Outside air 83. Calculated air volume (cfm) outside 317. Calculated air volume (cfm) return 67. Combined air volume (cfm) 384. ACH outside 2.3. ACH merv filter return air 0.5. ACH total 2.8. ACH Copy paste check (uses total or outside) 2.3. Room 103. % Outside air 50. Calculated air volume (cfm) outside 222. Calculated air volume (cfm) return 220. Combined air volume (cfm) 442. ACH outside 1.7. ACH merv filter return air 1.6. ACH total 3.3. ACH Copy paste check (uses total or outside) 1.7. |